| Plan Review Notes For Permit 14090908 |
| Permit Number |
14090908 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-01-28 05:32:58 | 1) CLEARLY SHOW THE INTERIOR DIMENSIONS OF THE ADA | | | SHOWER (L X W). THE DIMENSIONS ON SHT. A-1 ARE | | | ILLEGIBLE. THE PLANS SHALL BE DRAWN TO A MIN. 1/8 INCH | | | SCALE. SHT. A-1 IS CLEARLY NOT DRAWN TO AN 1/8 INCH | | | SCALE. WPB AMEND. TO 2010 FBC SEC.107.2.1, 107.2.1.4. | | | 2) THE ADA SHOWER DIMENSIONS APPEAR TO BE 38" X 39". | | | ACCESSIBLE TRANSFER SHOWERS SHALL BE 36" X 36" PER THE | | | FAC SEC.608.2. SEE SHEETS A-1 & A-6. | | | 3) SHT. A-6 - THE SEAT IN THE ACCESSIBLE SHOWER SHALL | | | COMPLY WITH THE FAC SEC.610.3.2. SHOW THIS ON THE | | | PLANS. SEE FIGURES 610.3.2 & 610.4 OF THE 2010 FAC. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|