2015-01-28 05:32:581) CLEARLY SHOW THE INTERIOR DIMENSIONS OF THE ADA
 SHOWER (L X W). THE DIMENSIONS ON SHT. A-1 ARE
 ILLEGIBLE. THE PLANS SHALL BE DRAWN TO A MIN. 1/8 INCH
 SCALE. SHT. A-1 IS CLEARLY NOT DRAWN TO AN 1/8 INCH
 SCALE. WPB AMEND. TO 2010 FBC SEC.107.2.1, 107.2.1.4.
 2) THE ADA SHOWER DIMENSIONS APPEAR TO BE 38" X 39".
 ACCESSIBLE TRANSFER SHOWERS SHALL BE 36" X 36" PER THE
 FAC SEC.608.2. SEE SHEETS A-1 & A-6.
 3) SHT. A-6 - THE SEAT IN THE ACCESSIBLE SHOWER SHALL
 COMPLY WITH THE FAC SEC.610.3.2. SHOW THIS ON THE
 PLANS. SEE FIGURES 610.3.2 & 610.4 OF THE 2010 FAC.
  