| Plan Review Notes For Permit 14090908 |
| Permit Number |
14090908 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-12-13 07:49:04 | 1 )SHT A-5 SHOWS ROOM 219 AS A HATCHED AREA FOR NO WORK | | | BEING DONE BUT SHTS.A-1 & D-2 SHOW THIS AS AN AREA | | | WHERE WORK IS BEING DONE. CLARIFY. | | | 2) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE ADA | | | SHOWER. COMPLY W/SEC.608.2.1 OF THE 2010FL. ACCESS. | | | CODE. | | | 3) PROVIDE AN ELEVATION DETAIL OF THE ADA SHOWER. THE | | | SHOWER SHALL HAVE A SEAT THAT COMPLIES W/ FAC | | | SEC.608.4. | | | 4) THE ADA SHOWER SHALL COMPLY W/FAC SEC. 608.2.1.FOR | | | ENTRY SIZE AND THE REQUIRED CLEAR FLOOR OUTSIDE OF THE | | | ENTRY WAY. | | | 5) GRAB BARS IN THE ADA SHOWER SHALL COMPLY W/ FAC | | | SEC.608.3.1. | | | 6) THE SHOWER CONTROLS SHALL COMPLY WITH 2010 FAC | | | SEC.608.5.1 | | | THE SINK IN BREAKROOM #218 IS NOT SHOWN ON THE SANITARY | | | OR WATER RISER DIAGRAMS. 2ND REQUEST. | | | 7) SIZE ALL SECTIONS OF THE VENTING SYSTEM ON SANITARY | | | RISER "B". | | | 8) SHT. P-2- REMOVE THE REFERENCE TO THE 2007 FBCAND | | | INSERT 2010 FBC. | | | 9) AS DESIGNED, THE WATER CLOSET IN ROOM 186 ON | | | SANITARY RISER "A" IS CREATING A HORIZONTAL WET VENT | | | AND DOES NOT COMPLY WITH 2010 FPC SEC.909.1 AS TO THE | | | TYPE AND NUMBER OF PLUMBING FIXTURES PERMITTED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|