2014-12-16 17:31:37PLAN DENIED
  
 1) SUBMIT A COMPLETE SET OF PLANS SHOWING
 ALL FOUR AIR CONDITIONING UNITS AND DUCT WORK.
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER ON EQUIPMENT TIE
 DOWN
 TO ROOF AND EQUIPMENT TIE DOWN TO STAND OR CURB
 PER SECTION 301.12 WIND RESISTANCE FBC (M) 2010
 3) SUBMIT ENERGY CALCULATIONS WITH THE PLANS
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010
 4) REFER TO SECTION 503.2.5.4 SHUT OFF DAMPER
 CONTROLS FLORIDA ENERGY CODE 2010
  
 PLAN REVIEW BY HAROLD MOSER