| 2014-12-15 16:51:12 | BUILDING PLAN REVIEW |
| | PERMIT: 14090908 |
| | ADD: 901 VILLAGE BLVD SUITE 702 |
| | CONT: PM BUILDERS |
| | TEL: (561)330-3833 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. DEC. 15/2014 |
| | ACTION: DENIED |
| | |
| | 1)COMPLIED. |
| | |
| | 2A) COMPLIED. |
| | PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE PHASED SCOPE |
| | OF WORK WITH EXIT SIGNS AND DIRECTIONAL SIGNAGE. 2010 |
| | FBC-B 1006.3.1 & 1006.3.8. |
| | |
| | 2B) NEW DESIGN AND THE TOTAL OCCUPANT LOAD FOR THE |
| | SPACE BEING 72 REQUIRES ALL DOORS TO SWING IN THE |
| | EGRESS PATH OF TRAVEL. 2010 FBC-B 1008.1.2. |
| | SEE THE DOOR BETWEEN THE WAITING ROOM 163 & HALL/ CHECK |
| | OUT ROOM # 173. |
| | |
| | 3) SHEET S-1 INDICATES THE USE OF NEW STOREFRONT |
| | WINDOWS AND DOORS. PLEASE PROVIDE COMPLIANCE WITH: |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5-7) COMPLIED. |
| | |
| | 8) NEW COMMENT. SHEET A-2 BATHROOM ROOM # 186 INDICATES |
| | THE USE OF A 18 INCH WIDE ADA BENCH. PLEASE REVIEW 2010 |
| | FBC- ACCESS. CODE 903.3 THE MINIMUM DEPTH OF THE BENCH |
| | IS 20 INCHES. ACCESS. CODE 903.4 WILL EITHER REQUIRE A |
| | BACK SUPPORT OR SECURED TO THE WALL. |
| | |
| | 9) BATHROOM # 186 PLEASE PROVIDE CODE COMPLIANCE FOR |
| | THE ADA SHOWER; |
| | 9A) PLEASE PROVIDE THE SIZE OF THE SHOWER 608.2. |
| | |
| | 9B) PLEASE SHOW COMPLIANCE WITH 608.2.1 TRANSFER TYPE |
| | SHOWERS. |
| | |
| | 9C) 608.3 GRAB BAR LOCATION & HEIGTH. |
| | |
| | 9D) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | |
| | 9E) 608.4 SEATS. |
| | |
| | 9F) 608.5. CONTROLS |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | 608.2.1 |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |