2014-10-20 10:37:411) 5 % BUT NO LESS THAN ONE OF THE SINKS IN THE EXAM
 ROOMS AND OTHER ROOMS SHALL COMPLY WITH THE 2010
 FLORIDA ACCESSIBILITY CODE SECS. 212.3, 306, & 606.
 2) SHT. P-2 - SIZE ALL SECTIONS OF THE SANITARY AND
 WATER RISER DIAGRAMS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) SHT. P-2 - DRAINS FOR SINKS IN ROOMS 187 & 188 ARE
 DRAWN IN THE OPPOSITE DIRECTION OF FLOW AT THE
 CONNECTION TO THE EXISTING LINE.
 4) SHT. P-2 - THE HUB DRAIN IN ROOM #205 REQUIRES A
 TRAP SEAL PER THE 2010 FPC SECS. 1002.1, 1002.4.
 5) SHT. P-2 - THE BREAK ROOM SINK IS NOT SHOWN ON THE
 SANITARY RISER. WPB AMEND. TO 2010FBC SEC.107.2.1.
 6) THE SINK IN RM. #188 IS NOTED AS EXISTING ON THE
 SANITARY RISER BUT AS NEW ON THE WATER RISER. CLARIFY.
  