Plan Review Notes
Plan Review Notes For Permit 14090908
Permit Number 14090908
Review Stop M
Sequence Number 1
Notes
Date Text
2014-10-08 13:26:14SHOW SIZE AND ROUTE OF EXHAUST DUCT TO OUTSIDE BLDG
 SHOW DUCT SIZES, CFM, MATERIAL AND INSULATION R-VALUE
 SHOW DISTANCE BETWEEN AIR INTAKES TO EXH. OR VENTS (10
 FT MIN )
 INDICATE WHICH EQUIPMENT IS NEW OR USED
 THERE ARE 2 RTU UNITS LABELED #1 ON THE SCHEDULE
 IF ANY OF THE A/C EQUIPMENT IS NEW , SUBMIT LOAD CALC'S
 FOR THAT AREA


Account Summary | Usage Policy | Privacy Policy