2014-10-01 14:25:05BUILDING PLAN REVIEW
 PERMIT: 14090908
 ADD: 901 VILLAGE BLVD SUITE 702
 CONT: PM BUILDERS
 TEL: (561)330-3833
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 01 /2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE SPRINKLERED OR NOT THIS WILL AFFECT TRAVEL LENGTHS
 AND DEAD ENDS.
  
 2A) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE PHASED
 SCOPE OF WORK WITH EXIT SIGNS AND DIRECTIONAL SIGNAGE.
 2010 FBC-B 1006.3.1 & 1006.3.8.
  
 2B) THE ELECTRICAL SHEETS SHOW A EXIT SIGN THROUGH THE
 NEURO FEEDBACK ROOM, 2010 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES 4. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES. ROOMS THAT CAN BE LOCKABLE.
  
 3) SHEET S-1 INDICATES THE USE OF NEW STOREFRONT
 WINDOWS AND DOORS. PLEASE PROVIDE COMPLIANCE WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS,
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) INTERIOR DECORATOR PLANS DESIGNED BY P2 INTERIORS,
 LICENSE # IB26001537 ARE NOT SIGNED NOR SEALED.
 61G1-16.003 USE OF SEAL. EFFECTIVE 04/18/2000 THE
 PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT OR
 INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD.
  
 6) IMPACT FEES- NOT REQUIRED.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]