| 2014-10-14 13:04:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | SEE FBC 3103, TEMPORARY STRUCTURES. THE FOLLOWING ITEMS | | | ARE REQUIRED: | | | | | | FROM PROVISO LIST: | | | | | | 1. 3103.3, TEMPORARY STRUCTURES SHALL BE LOCATED IN | | | ACCORDANCE WITH THE REQUIREMENTS OF TABLE 602. IT IS | | | NOT CLEAR WHETHER THIS IS ATTACHED TO AN EXISTING | | | BUILDING OR FREE STANDING, AND IF IT IS ATTACHED TO AN | | | EXISTING BUILDING, HOW THE PROPOSED TENT WILL AFFECT | | | THE EXITING FOR THE EXISTING BUILDING. | | | | | | THE SITE PLAN SUBMITTED IS ILLEGIBLE. IT IS A COLOR | | | AERIAL WITH WHAT APPEARS TO BE WORDS, ALL IN COLOR, | | | NONE OF IT LEGIBLE. PLANS SHOULD BE LEGIBLE, | | | ARCHITECTURAL QUALITY, FBC 107. PROVIDE A LEGIBLE SITE | | | PLAN WHICH PROVIDES INFORMATION REQUIRED. | | | | | | 2. 3103.2, CONSTRUCTION DOCUMENTS ARE TO INCLUDE | | | INFORMATION DELINEATING THE MEANS OF EGRESS AND | | | OCCUPANT LOAD. PLAN AND OCCUPANT NOT CLEAR. | | | | | | SEE FBC TABLE 1004.1. IT APPEARS THAT THE ENCLOSED | | | ASSEMBLY AREA IS 82X66, 5412 SF. PER TABLE, THIS | | | RESULTS IN AN OCCUPANT LOAD OF 361. PLEASE REVISE PLAN | | | TO INCLUDE OCCUPANT LOAD. | | | | | | PLEASE BE AWARE THAT THIS IS THE NUMBER FOR WHICH YOU | | | ARE REQUIRED TO DESIGN EXITING, NOT THE NUMBER OF | | | OCCUPANTS ALLOWED (THIS IS DETERMINED BY FIRE). | | | | | | |
|