| 2014-10-14 12:14:24 | 10/14/2014 |
| | PROJECT: LIFE IN PALM BEACH "SIGN " |
| | PERMIT#: |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 600.3 LISTING. |
| | ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| | FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| | OTHERWISE APPROVED BY SPECIAL PERMISSION. INDICATE THE |
| | REQUIRED LISTING AND LABELING PER NEC 600.3 AND NEC |
| | 110.3(B) |
| | |
| | 2) NEC 600.5 |
| | EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| | A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. INDICATE THE REQUIRED SIGN |
| | CIRCUIT IS EITHER EXISTING TO REMAIN OR PROPOSED TO BE |
| | INSTALLED UNDER THIS SCOPE. IF IT IS TO BE INSTALLED |
| | UNDER THIS SCOPE A SEPARATE PERMIT BY A QUALIFIED |
| | ELECTRICAL CONTRACTO IS REQUIRED. |
| | |
| | 3) NEC 600.6(A)(1) LOCATION. |
| | DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR |
| | FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR |
| | OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN |
| | EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL |
| | OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN |
| | OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. INDICATE |
| | THE REQUIRED DISCONNECT WITHIN SIGHT OF THE SIGN. |
| | |
| | 4) FBC-E 505.2.4 |
| | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| | OF POWER FOR A MINIMUM OF 10 HOURS. THE DEDICATED SIGN |
| | CIRCUIT SHALL COMPLY WITH THE PROVISIONS OF THE FBC-E |
| | 505.2.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |