Plan Review Notes
Plan Review Notes For Permit 14090842
Permit Number 14090842
Review Stop E
Sequence Number 3
Notes
Date Text
2014-12-02 15:24:25DATE: 12/2/2014
 PROJECT: DUPONT RENNOVATION
 PERMIT#: 14090842
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
  
 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
 REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND
 WHICH ARE EXISTING CIRCUITS THROUGHOUT. AND PROVIDE
 EACH CIRCUIT WITH IT'S CLEAR EVIDENT AND SPECIFIC
 PURPOSE. SEE NEC 408.4
  
 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON
 THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL
 CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C
 CONDESNSING UNITS CIRCUITS
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT
 CALCULATION.
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) CLARIFICATION REQUIRED FOR THE OPERATION OF THE
 OCCUPANCY SENSOR SWITCHES ON THE PROPOSED 1ST FL
 ELECTRICAL PLAN. PLEASE INDICATE HOW THE OSS IS
 PROPOSED TO CONTROL THE MULTIPLE LIGHTING CIRCUITS
 INDICATED ON THE FLOOR PLAN. FBC 505.2.
  
 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS
 CONTROL SYSTEM.
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved