Plan Review Notes
Plan Review Notes For Permit 14090842
Permit Number 14090842
Review Stop B
Sequence Number 3
Notes
Date Text
2014-12-02 06:52:59BUILDING PLAN REVIEW
 PERMIT: 14090842
 ADD: 431 BUNKER RD
 CONT: SULLIVAN BUILDERS OF FL.
 TEL: (561) 310-1899
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 ***********NOTICE**********:CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 3RD REVIEW
 DATE: TUES. DEC. 02/ 2014
 ACTION: DENIED
  
 1) COMPLIED.
 COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE AND
 BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE FEET
 THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA.
  
 2) COMPLIED. OCCUPANCY S-1
  
 3) COMPLIED. OCCUPANCY S-1 7815/300= 27 NOT 26.
  
 4) #RD REQUEST. THE DESIGNER OF RECORD HAS DECALRED
 THIS TO BE A LEVEL 2 ALTERATION. PLEASE REVIEW SECTION
 2010 FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART
 OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT
 A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON
 THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW
 FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED
 BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A
 MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3. THE FLOOR
 AREA OF THE 2ND FLOOR IS 48% OF THE 1ST FLOOR.
  
 NOTE; THE REMOVAL OF STIAR ENCLOSURES CREATES A
 NON-CONFORMITY, UNDER PERMIT # 13060708 PLANS SHOWED AN
 EXISTING STAIR ENCLOSURE. A NEW EXTERIOR DOOR WAS TO BE
 INSTALLED IN THE EXTERIOR WALL SO THE 2ND FLOOR TENANTS
 WOULD BE ABLE TO EXIT THE ENCLOSURE WITHOUT GOING
 THROUGH THE OTHER TENANTCY.
  
 5 ) 3RD REQUEST. COVER SHEET. COMMON PATH OF TRAVEL
 FROM THE MOST REMOTE POINT UPSTAIRS IN THE STORAGE AREA
 TO AN EXIT CAN BE UP TO 100 FT FOR STORAGE NON
 SPRINKLERRED BUILDING WITH AN OCCUPANT LOAD OF LESS
 THAN 30. (FBC-B 1014.3EXC. # 2) . THE TRAVEL DISTANCE
 FROM THE MOST REMOTE POINT APPROX. 105 FT.
  
 6) COMPLIED.
 PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE
 ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS.
 206.4 ENTRANCES.
 ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4.
 ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH
 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH
 402.
  
 7) COMPLIED.
 SHOWING LIFT DISPROPORTIONATE. PLEASE SHOW COMPLIANCE
 WITH AN ACCESSIBLE ROUTE TO THE 2ND FLOOR. 2010
 FBC-ACC. CODE
 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH
 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT
 OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN
 ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE
 PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN
 EXISTING BUILDING OR FACILITY.
 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY,
  
  
  
 8) COMPLIED
 . SHOWING LIFT IS DISPROPORTIONATE. PLEASE PROVIDE
 COMPLIANCE WITH 2010 FL ACC. CODE 202.4.1
 DISPROPORTIONATE COST. THE CONTRACTOR IS TO CREATE ON
 THEIR OWN LETTER HEAD AN ITEMIZED LIST WHERE $14,000.00
 IN ACCESSIBLE UPGRADES IN THE LISTED ORDER BELOW.
 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 9)COMPLIED.
 PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 10) THE PRODUCT APPROVALS SUBMITTED WERE NOT REVIEWED
 BY THE DESIGNER OF RECORD, NO SHOP DRAWING STAMP OF
 APPROVAL. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  