2014-11-15 10:48:241) SHT.2 OF 3 - SANITARY ISOMETRIC - THE FIRST FLOOR
 WATER CLOSET CANNOT BE VERTICALLY WET VENTED BY THE
 SECOND FLOOR SOIL STACK/BATHROOM GROUP PERR SEC.909.1.1
 OF THE 2010 FLORIDA PLUMBING CODE. THE CONNECTION FOR
 THE 2ND FLR. SHALL CONNECT EITHER UPSTREAM OR
 DOWNSTREAM FROM THE LAV/DRINKING FOUNTAIN CONNECTION
 POINT TO THE 4" BUILDING DRAIN BUT CANNOT CONNECT AT
 THE SAME POINT AS DRAWN.
 2) CLEANOUTS ARE REQD. IN THE BASE OF THE SOIL STACKTO
 THE SECOND FLOOR PER FPC SEC.708.3.4.
 3)CLEARLY SHOW ON THE PLANS THAT THE DRINKING FOUNTAIN
 COMPLIES WITH THE FAC SECS.602.1 THROUGH 602.7.
 4)THE CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAINS
 SHALL BE CENTERED ON EACH UNIT.THE PLANS SHOW THE CLEAR
 FLOOR SPACE CENTERED ON BOTH UNITS. COMPLY W/ 2010 FAC
 SEC. 602.2.
  