| 2014-11-18 13:01:22 | PLAN DENIED | | | | | | 1) PROVIDE THE SIGNATURE AND LICENSE NUMBER OF WHO EVER | | | DREW THE PLANS | | | ON THE PLAN. | | | 2) PROVIDE A DETAIL FROM A ENGINEER ON THE CONDENSER | | | STAND TIE DOWN TO | | | THE ROOF, AND CONDENSER TO STAND TIE DOWN. PER SECTION | | | 301.12 | | | WIND RESISTANCE 2010 FBC (M) | | | 3) SHOW ROOF ACCESS ON PLAN PER SECTION 306.5 EQUIPMENT | | | AND APPLIANCES ON ROOF OR ELEVATED STRUCTURES. 2010 FBC | | | (M) | | | 4) REFER TO SECTION 304.11 GUARDS. | | | 5) AIR HANDLER DETAIL SHOWS CLOSET TO BE A RETURN AIR | | | PLENUM. | | | REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|