| 2014-11-19 11:58:34 | DATE: 11/19/2014 |
| | PROJECT: DUPONT RENNOVATION |
| | PERMIT#: 14090842 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL |
| | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT |
| | CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE |
| | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE |
| | FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| | PANELBOARD, AND LOCATED AT EACH SWITCH ON A |
| | SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER |
| | THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
| | REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND |
| | WHICH ARE EXISTING CIRCUITS THROUGHOUT. NEC 408.4 |
| | |
| | 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON |
| | THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL |
| | CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C |
| | CONDESNSING UNITS CIRCUITS |
| | |
| | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT |
| | CALCULATION. |
| | |
| | 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 5) CLARIFICATION REQUIRED FOR THE SYMBOL IDENTIFIED AS |
| | AN OCCUPANCY SENSOR SWITCH THAT IS SHOWN AT THE EGRESS |
| | DOORS ON THE PROPOSED 1ST FL ELECTRICAL PLAN. THERE ARE |
| | ALSO 3WAY SWITCHES INDICATING THE CONTROL OF THE |
| | LIGHTING FOR THE SPACE. PLEASE INDICATE COMPLIANCE TO |
| | THE FBC 505.2.4 LIGHTING SYSTEMS SHALL BE PROVIDED WITH |
| | CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, |
| | 505.2.3 AND 505.2.4. |
| | |
| | 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA, |
| | COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS |
| | CONTROL SYSTEM. |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |