2014-11-19 11:58:34DATE: 11/19/2014
 PROJECT: DUPONT RENNOVATION
 PERMIT#: 14090842
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
 REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND
 WHICH ARE EXISTING CIRCUITS THROUGHOUT. NEC 408.4
  
 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON
 THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL
 CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C
 CONDESNSING UNITS CIRCUITS
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT
 CALCULATION.
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) CLARIFICATION REQUIRED FOR THE SYMBOL IDENTIFIED AS
 AN OCCUPANCY SENSOR SWITCH THAT IS SHOWN AT THE EGRESS
 DOORS ON THE PROPOSED 1ST FL ELECTRICAL PLAN. THERE ARE
 ALSO 3WAY SWITCHES INDICATING THE CONTROL OF THE
 LIGHTING FOR THE SPACE. PLEASE INDICATE COMPLIANCE TO
 THE FBC 505.2.4 LIGHTING SYSTEMS SHALL BE PROVIDED WITH
 CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2,
 505.2.3 AND 505.2.4.
  
 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS
 CONTROL SYSTEM.
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  