Plan Review Notes
Plan Review Notes For Permit 14090842
Permit Number 14090842
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-27 09:55:001) SHT.2 OF 3 - SANITARY ISOMETRIC - THE FIRST FLOOR
 WATER CLOSET CANNOT BE VERTICALLY WET VENTED BY THE
 SECOND FLOOR SOIL STACK/BATHROOM GROUP PERR SEC.909.1.1
 OF THE 2010 FLORIDA PLUMBING CODE.
 2) SIZE THE VENT FOR THE 1ST. FLR LAVATORY.
 3) SIZE THE VENT FOR THE DRINKING FOUNTAIN.
 4) CLEANOUTS ARE REQD. IN THE BASE OF THE WASTE/SOIL
 STACKS PER SEC.708.3.4.
 4) SHOW THE REQUIRED TOE CLEARANCES FOR THE LAVATORY
 AND DRINKING FOUNTAINS PER THE 2010 FL. ACCESS. CODE.
 SEC.306.2.
 5) SHOW THE REQUIRED KNEE CLEARANCES FOR THE LAVATORY
 AND DRINKING FOUNTAINS PER THE 2010 FAC SEC. 306.3.
 6) CLEARLY SHOW ON THE PLANS THAT THE DRINKING FOUNTAIN
 COMPLIES WITH THE FAC SECS.602.1 THROUGH 602.7.
 7) THE CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAINS
 SHALL BE CENTERED ON EACH UNIT.THE PLANS SHOW THE CLEAR
 FLOOR SPACE CENTERED ON BOTH UNITS. COMPLY W/ 2010 FAC
 SEC. 602.2.
 8) SUBMIT ENLARGED HANDICAPPED BATHROOM AND DRINKING
 FOUNTAIN PLAN THAT CLEARLY SHOWS THE REQUIRED CLEAR
 FLOOR SPACE DIMENSIONS AND ALSO THE LOCATION OF THE
 GRAB BARS. THE DETAILS ON THE PLAN ARE NOT
 CLEAR/LEGIBLE. THE GRAB BARS SHALL BE LOCATED PER SECS.
 604.5.1 & 604.5.2 OF THE 2010 FAC.
 9) A SHUT OFF VALVE IS REQD. ON THE WATER PIPE RISER TO
 THE 2ND FLOOR BATH PER THE 2010 FPC SEC. 606.1 (4).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  