| 2014-10-03 13:24:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | A STORAGE OCCUPANCY SHALL COMPLY WITH NFPA 101, FLORIDA |
| | LIFE SAFETY CODE, FLORIDA 2010 EDITION. |
| | |
| | SHEET 1 OF 3 INDICATES THAT THE PREVIOUS OCCUPANCY AND |
| | PROPOSED OCCUPANCY AS BUSINESS/STORAGE. HOWEVER, SHEET |
| | 2 OF 3 DOES NOT INDICATE ANY BUSINESS SPACES. PLEASE |
| | INDICATE AND/OR IDENTIFY THE OCCUPANY BUSINESS INTENT |
| | AND THE AREAS OF BUSINESS WITHIN THE OCCUPANY. |
| | |
| | IF THIS IS A MIXED OCCUPANY, PLEASE INDICATE SUCH AND |
| | THE PROPOSED CHAPTER/PROVISION YOU ARE COMPLYING WITH. |
| | |
| | IDENTIFY THE PROPOSED STORAGE TYPE AND |
| | COMMODITY/MATERIAL BEING STORED. |
| | |
| | SHEET 2 OF 3 INDICATES THE MAX NUMBER OF EMPLOYEES PER |
| | SHIFT = 2. WHAT CONSTITUTES A SHIFT? WILL THERE BE |
| | MANUFACTURING OR WORK BEING PRODUCED? WILL THE GENERAL |
| | PUBLIC BE VISITING OR PATRONIZING THIS STORAGE |
| | OCCUPANCY? |
| | |
| | |
| | IDENTIFY THE EXISTING AND PROPOSED LIFE SAFETY FEATURES |
| | AND SYSTEMS FOR THE BUILDING. |
| | |
| | SHEET 2 OF 3 INDICATES THE ADDITON OF ADDITIONAL |
| | INTERIOR WALLS. SHEET 3 OF 3 INDICATES 1 EXIT EMERGENCY |
| | LIGHT AND 1 EMERGENCY LIGHT ON THE 1ST FLOOR. |
| | ADDITIONAL EXIT SIGNAGE EMERGENCY LIGHTING IS REQUIRED |
| | TO ILLUMINATE THE THE EXIT PASSAGE FROM THE REST ROOM |
| | AREA AND THE INTERIOR DOOR BY THE REST ROOM. |
| | |
| | SHEET 2 OF 3 DOES NOT INDICATE AN EMERGENCY LIGHT |
| | ILLUMINATING THE EXIT STAIR. |
| | |
| | BASED ON THE STORAGE AND COMMODITY TYPE YOU WILL BE |
| | PROVIDING THE COMMON PATH OF TRAVEL FROM THE SECOND |
| | FLOOR AND AND THE FIRST FLOOR BATHROOM AREA MAY EXCEED |
| | THE 50FT MAXIMUM OF ORDINARY HAZARD STORAGE. |
| | |
| | |