Plan Review Notes
Plan Review Notes For Permit 14090842
Permit Number 14090842
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-24 10:35:18DATE: 9/24/2014
 PROJECT: DUPONT RENNOVATION
 PERMIT#: 14090842
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE PANEL SCHEDULES TO INCLUDE ALL A/C UNITS AND
 AND RECEPTACLE CIRCUITS THROUGHOUT.
  
 2) REVISE LOAD CALCULATION TO INCLUDE LOADS FOR ALL
 CIRCUITS IN REVISED PANEL SCHEDULES INCLUDING ALL A/C
 AND HEATING LOADS.
  
 3) REVISE RISER DIAGRAM TO INCLUDE THE GROUNDING
 ELECTRODE SYSTEM DETAIL, AS WELL AS CONDUIT AND WIRE
 SIZES AND TYPES.
  
 4) REVISE FLOOR PLAN TO INCLUDE CIRCUITING FOR OUTLETS,
 LIGHTING AND EQUIPMENT TO CORESPOND TO REVISED PANEL
 SCHEDULES.
  
 5) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC
 700.12(F) CIRCUIT THE EMERGENCY AND EXIT LIGHTING TO BE
 WIRED AHEAD OF ANY SWITCHING AND ON THE SAME CIRCUIT
 AND THE GENERAL LIGHTING IN THE AREA THEY SERVE. NEC
 700.12(F)
 B.)EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 ADDITIONAL
 EMERGENCY FIXTURES WILL BE REQUIRED TO ACCOMPLISH THIS.
 SEE AREAS AT STAIRWELL AND AREAS BETWEEN NEW
 PARTITIONS. NEC 700.16
  
 6) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC - ENERGY 505.3
  
 7) LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN FBC - ENERGY 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL
 BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT
 OFF LIGHTING IN THOSE AREAS. FBC 505.2.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  