| Plan Review Notes For Permit 14090789 |
| Permit Number |
14090789 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-27 07:45:18 | 1) SECTION 616.1 OF THE 2010 FUEL GAS CODE MANDATES | | | THAT THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE | | | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND | | | NFPA 37. NFPA 37 REQUIRES THE GENERATOR TO BE A MIN. OF | | | 5 FT. FROM OPENINGS IN WALLS AND 5 FT. FROM STRUCTURES | | | HAVING COMBUSTIBLE WALLS UNLESS THE WALL IS FIRE RATED | | | WITH A RATING OF AT LEAST ONE HOUR OR THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE | | | THE ENCLOSURE. THE GENERATOR IS SHOWN 18 INCHES FROM | | | THE BUILDING WALLS. | | | 2) SHOW THAT THE GENERATOR IS A MIN. 5 FT. AWAY FROM | | | ALL BUILDING OPENINGS. | | | 3) SUBMIT 2 COPIES OF THE MANUF. INSTALLATION | | | INSTRUCTIONS FOR THE GENERATOR. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|