| Plan Review Notes For Permit 14090787 |
| Permit Number |
14090787 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-23 18:18:24 | RESIDENTIAL (R2) FLOORING, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SOUND INSULATION MATERIALS: PROVIDE 2 COPIES OF THE | | | FLAME SPREAD INDEX AND SMOKE- DEVELOPED INDEX TEST IN | | | ACCORDANCE WITH ASTM E 84 OR UL 723 AS REQUIRED BY SEC. | | | 719.1 OF 2010 FBC. | | | | | | 2- A) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS | | | (STC) TEST SHOWING COMPLIANCE WITH ASTM E90 AS REQUIRED | | | BY SEC. 1207.2 OF 2010 FBC.. | | | B) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS | | | (IIC) TEST SHOWING COMPLIANCE WITH ASTM E 492 AS | | | REQUIRED BY SEC. 1207.3 OF 2010 FBC. | | | | | | ***NOTE: INFORMATION SUBMITTED STATES "INDEPENDENT | | | SOUND TESTED. IIC=70MIN STC=67MIN". BUT, THERE IS NO | | | INFORMATION ABOUT THE INDEPENDENT TEST PERFORMED. NEED | | | TO KNOW THE STANDARDS USED FOR THE TEST AND IF THE TEST | | | WAS DONE WITH SUSPENDED CEILING ASSEMBLY OR NOT? AND | | | THICKNESS OF CONCRETE SLAB, ETC. OTHERWISE IF ASSEMBLY | | | DOESN'T MATCH PROPOSED APPLICATION, THEN IT MAY NOT BE | | | USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|