| Plan Review Notes For Permit 14090778 |
| Permit Number |
14090778 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-27 08:45:55 | 1) THE DOCUMENT FROM FLORIDA SEPTIC TANK REFERS TO THE | | | 2007 FLORIDA PLUMBING CODE. THE PLUMBING CODE IN EFFECT | | | IS THE 2010 FLORIDA PLUMBING CODE. THE INTERCEPTOR | | | SHALL COMPLY W/ THE 2010 CODE. | | | 2) THE INLET INVERT SHALL DISCHARGE A MINIMUM 2 1/2 | | | INCHES ABOVE THE LIQUID LEVEL LINE AND THE OUTLET PIPE | | | SHALL HAVE A TEE WITH A MINIMUM DIAMETER OF 4 INCHES | | | THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM OF THE | | | TANK. THE TEE SHALL BE INSTALLED WITH THE RUN IN THE | | | VERTICAL DIRECTION PER SEC. 1003.5.3 OF THE 2010 FL. | | | PLUMBING CODE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|