| 2014-09-26 12:04:42 | BUILDING PLAN REVIEW |
| | PERMIT: 14090761 |
| | ADD: 2401 MERCER AVE BUILDING B |
| | CONT: GREENVIEW CONTRACTOR |
| | TEL: (561) 727-5013 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. SEPT. 26/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2 INDICATES UNDER THE HEADING CODE SUMMARY |
| | THIS BUILDING O BE A TYPE IV BUILDING WHICH IS HEAVY |
| | TIMBER CONSTRUCTION. PLEASE VERIFY TYPE OF |
| | CONSTRUCTION. 2010 FBC-B TABLE 601. |
| | |
| | 2) THE DESIGNER OF RECORD HAS NOT DECLARED UNDER THE |
| | 2010 FL EXISTING BUILDING CODE AS TO WHICH OF THE |
| | COMPLIANCE METHODS THE RENOVATION WAS DESIGNED. 2010 FL |
| | EXST BLDG CODE 101.5. FOR THE PURPOSE OF THIS REVIEW, I |
| | AM GOING TO REVIEW UNDER THE WORK AREA METHOD AS A |
| | LEVEL II ALTERATION. 2010 EXISTING BUILDING CODE LEVEL |
| | II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3) THE DESIGNER OF RECORD HAS INDICATED ON SHEET A-2 |
| | THE AREA NOT TO BE INCLUDED IN THE WORK AREA AS N.I.C. |
| | THE REST OF THE BUILDING WILL BE REVIEWED AS THE AREA |
| | OF WORK TO BE COMPLETED AND IS TO BE REVIEWED FOR CODE |
| | COMPLIANCE. |
| | |
| | 3A) THE CODE SUMMARY INDICATES THIS OCCUPANCY AS A |
| | EDUCATIONAL OCCUPANCY, NON-SPRINKLERED, THE PLANS FAIL |
| | TO INDICATE THE CORRIDOR WALLS TO BE 1 HOUR FIRE RATED |
| | WITH FIRE RATED DOORS SEE TABLE 715.4 AND TABLE 1018.1. |
| | |
| | 3B) THE PLANS DO NOT INDICATE ANY DOOR SCHEDULE NOR |
| | HARDWARE FOR EGRESS DOORS. SHOW COMPLIANCE FOR |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A |
| | GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES |
| | WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E |
| | OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK |
| | UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 4C) THE OTHER ISSUE IS THIS IS A NON-SPRINKLERED |
| | BUILDING, EDUCATIONAL OCCUPANCY AND COMPLIANCE WITH |
| | SECTION 2010 FBC-B 1029.4.1 |
| | EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2 |
| | M2) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR |
| | OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO |
| | STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY |
| | SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS. |
| | 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20 |
| | INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT, |
| | AND 5.7 SQUARE FEET (0.53 M2) IN AREA. |
| | 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING |
| | DEVICE SHALL BE CAPABLE |
| | OF BEING OPERATED FROM NOT MORE THAN 54 INCHES (1372 |
| | MM) ABOVE THE FINISHED FLOOR. |
| | |
| | 4D) NOTE AT THIS TIME NO MECHANICAL PLANS WERE PROVIDED |
| | TO VERIFY CODE COMPLIANCE WITH 2010 FBC-B 716.1.1 DUCTS |
| | THAT PENETRATE FIRE-RESISTANCE-RATED ASSEMBLIES WITHOUT |
| | DAMPERS. DUCTS THAT PENETRATE FIRE-RESISTANCE-RATED |
| | ASSEMBLIES AND ARE NOT REQUIRED BY THIS SECTION TO HAVE |
| | DAMPERS SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS |
| | 713.2 THROUGH 713.3.3. DUCTS THAT PENETRATE HORIZONTAL |
| | ASSEMBLIES NOT REQUIRED TO BE CONTAINED WITHIN A SHAFT |
| | AND NOT REQUIRED BY THIS SECTION TO HAVE DAMPERS SHALL |
| | COMPLY WITH THE REQUIREMENTS OF SECTIONS 713.4 THROUGH |
| | 713.4.2.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |