Plan Review Notes
Plan Review Notes For Permit 14090756
Permit Number 14090756
Review Stop B
Sequence Number 3
Notes
Date Text
2015-03-27 15:05:22PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) REVISE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS TO CORRESPOND WITH THE INCREASED
 PRESSURES FOR EXPOSURE D. FBC - R301.2.1 THE EXPOSURE
 CATEGORY WAS CHANGED FROM C TO D, BUT THE PRESSURES
 WERE NOT CHANGED.
  
 2) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. (ENERGY CALCS.) THE PLANS SPECIFY THAT THE
 AIR HANDLER FOR THE ADDITION IS LOCATED IN THE ATTIC.
 ENERGY FORM 402 CAN NOT BE USED WHEN THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE SUBMITTALS
 FOR THE ASPHALT SHINGLE ROOFING.
  
 4) FBC R704 IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). THE
 STUCCO STOP / WEEP SCREED IS REQUIRED TO BE 6 INCHES
 ABOVE FINAL EXTERIOR GRADE.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  