| 2015-02-02 09:52:49 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | MECHANICAL DENIED |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE MECHANICAL PLANS SHOW TWO SEPARATE HVAC SYSTEMS. |
| | ONE IS FOR THE NEW ADDITION AND THE OTHER IS FOR THE |
| | EXISTING DWELLING. IF A NEW HVAC SYSTEM IS BEING |
| | INSTALLED IN THE EXISTING DWELLING, THEN THE ENTIRE |
| | SYSTEM IS REQUIRED TO COMPLY WITH THE 2010 FBC. PLEASE |
| | CLARIFY. FBC 107.2.1 |
| | |
| | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| | |
| | 3) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT |
| | BEDROOMS. |
| | |
| | 4) FBC 107.2.1 SPECIFY THE CFMS AT THE SUPPLY OUTLETS. |
| | |
| | 5) THERE IS A CONFLICT BETWEEN THE ELECTRICAL PLANS AND |
| | THE MECHANICAL PLANS. THE ELECTRICAL PLAN SHOWS A |
| | MINI-SPLIT SYSTEM IN THE NEW ADDITION AND THE |
| | MECHANICAL PLAN SHOWS A DUCTED SYSTEM WITH THE AIR |
| | HANDLER IN THE ATTIC. PLEASE COORDINATE THE MECHANICAL |
| | INFORMATION. FBC 107.2.1 |
| | |
| | 6) FBC-R - M1305.1.3 APPLIANCES IN ATTICS. |
| | ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN |
| | OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE |
| | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT |
| | NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES |
| | (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG |
| | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM |
| | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE |
| | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 |
| | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| | SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES |
| | (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE |
| | APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS |
| | OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY |
| | 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW |
| | REMOVAL OF THE LARGEST APPLIANCE. |
| | |
| | 7) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| | ACCORDANCE WITH CHAPTER 34. |
| | |