Plan Review Notes
Plan Review Notes For Permit 14090756
Permit Number 14090756
Review Stop E
Sequence Number 2
Notes
Date Text
2015-02-02 11:41:41DATE: 02/02/2015
 PROJECT: 221 PURITAN RD
 PERMIT#: 14090756
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) MINIMUM PLAN REVIEW CRIERIA REQUIRES A RISER
 DIAGRAM, PANEL SCHEDULE AND FLOOR PLAN DETAILING
 CIRCUIT NUMBERS AT EACH OUTLET, DEVICE AND EQUIPMENT
 LOCATIONS. WPB AMENDMENTS FBC 107.3.2
 THERE IS STILL NO PANEL SCHEDULE AND NO CIRCUIT NUMBERS
 ON THE FLOOR PLAN.
  
 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.702) INDICATE THE
 LOCATION OF THE MAIN BREAKER AND THE PANEL ON THE FLOOR
 PLAN.
  
 3) THE MECHANICAL PLANS SUBMITTED ARE CONFLICTING WITH
 THE ELECTRICAL PLAN. PROVIDE A COHESIVE PLAN THE IS
 COORDINATED WITHE THE MECHANICAL PLANS. PROVIDE THE
 CIRCUIT NUMBERS WITH THE PROPPER OCPD AND WIRE SIZES
 ASSOCIATED WITH EACH CIRCUIT ANDINDICATE THE CIRCUIT
 NUMBERS ON THE FLOOR PLAN.
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 7) BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. INDICATE THE
 REQUIRED 20AMP BRANCH CIRCUIT IN THE PANEL SCHEDULE AND
 ON THE FLOOR PLAN. INDICATE THE CORRESPONDING WIRE
 SIZES IN THE PANEL SCHEDULE FOR EACH NEW CIRCUIT OCPD.
  
 8) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315. THIS ARTICLE CALLS FOR SMOKE DETECTORS TO
 BE INSTALLED AND INTERCONNECTED INSIDE AND OUTSIDE OF
 ALL SLEEPING ROOMS. THERE IS ONLY A PARTIAL FLOOR PLAN
 SHOWN. EITHER PROVIDE A COMPLETE FLOOR PLAN INDICATING
 ALL REQUIRED SMOKE DETECTORS OR PROVIDE A NOTE THAT
 THEY ARE REQUIRED AS DECRIBED IN THE FBC SECTION 314
 AND 315 FOR CO DETECTORS.
  
 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1. THE PLANS ARE STILL NOT SIGNED. THE
 DESIGN MUST BEAR THE NAME AND SIGNATURE OF THE PERSON
 REPSONIBLE FOR THE DESIGN.
  
 10) UNDER ELECTRICAL NOTES THE ELECTRICAL CODE VERSION
 IS INDICATED AS 2010. THE ACTUAL NATIONAL ELECTRICAL
 CODE IN EFFECT AT THIS TIME IS 2008. ADJUST PLANS
 ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  