| 2015-02-02 11:41:41 | DATE: 02/02/2015 |
| | PROJECT: 221 PURITAN RD |
| | PERMIT#: 14090756 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) MINIMUM PLAN REVIEW CRIERIA REQUIRES A RISER |
| | DIAGRAM, PANEL SCHEDULE AND FLOOR PLAN DETAILING |
| | CIRCUIT NUMBERS AT EACH OUTLET, DEVICE AND EQUIPMENT |
| | LOCATIONS. WPB AMENDMENTS FBC 107.3.2 |
| | THERE IS STILL NO PANEL SCHEDULE AND NO CIRCUIT NUMBERS |
| | ON THE FLOOR PLAN. |
| | |
| | 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY |
| | ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF |
| | THE SERVICE CONDUCTORS. NEC 230.702) INDICATE THE |
| | LOCATION OF THE MAIN BREAKER AND THE PANEL ON THE FLOOR |
| | PLAN. |
| | |
| | 3) THE MECHANICAL PLANS SUBMITTED ARE CONFLICTING WITH |
| | THE ELECTRICAL PLAN. PROVIDE A COHESIVE PLAN THE IS |
| | COORDINATED WITHE THE MECHANICAL PLANS. PROVIDE THE |
| | CIRCUIT NUMBERS WITH THE PROPPER OCPD AND WIRE SIZES |
| | ASSOCIATED WITH EACH CIRCUIT ANDINDICATE THE CIRCUIT |
| | NUMBERS ON THE FLOOR PLAN. |
| | |
| | 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 |
| | |
| | 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | 7) BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER |
| | OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. INDICATE THE |
| | REQUIRED 20AMP BRANCH CIRCUIT IN THE PANEL SCHEDULE AND |
| | ON THE FLOOR PLAN. INDICATE THE CORRESPONDING WIRE |
| | SIZES IN THE PANEL SCHEDULE FOR EACH NEW CIRCUIT OCPD. |
| | |
| | 8) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. THIS ARTICLE CALLS FOR SMOKE DETECTORS TO |
| | BE INSTALLED AND INTERCONNECTED INSIDE AND OUTSIDE OF |
| | ALL SLEEPING ROOMS. THERE IS ONLY A PARTIAL FLOOR PLAN |
| | SHOWN. EITHER PROVIDE A COMPLETE FLOOR PLAN INDICATING |
| | ALL REQUIRED SMOKE DETECTORS OR PROVIDE A NOTE THAT |
| | THEY ARE REQUIRED AS DECRIBED IN THE FBC SECTION 314 |
| | AND 315 FOR CO DETECTORS. |
| | |
| | 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1. THE PLANS ARE STILL NOT SIGNED. THE |
| | DESIGN MUST BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | REPSONIBLE FOR THE DESIGN. |
| | |
| | 10) UNDER ELECTRICAL NOTES THE ELECTRICAL CODE VERSION |
| | IS INDICATED AS 2010. THE ACTUAL NATIONAL ELECTRICAL |
| | CODE IN EFFECT AT THIS TIME IS 2008. ADJUST PLANS |
| | ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |