Plan Review Notes
Plan Review Notes For Permit 14090756
Permit Number 14090756
Review Stop B
Sequence Number 2
Notes
Date Text
2015-02-02 09:52:19PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTRACOASTAL WATERWAY WHICH IS EXPOSURE D, THEREFORE,
 THIS STRUCTURE IS EXPOSURE CATEGORY D. PLEASE CORRECT
 SHEET S-1 AND REVISE THE COMPONENT AND CLADDING
 PRESSURES ACCORDINGLY.
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING
 HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D
 CONDITION AS DEFINED IN THE PREVIOUS SENTENCE.
  
 2) REVISE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS TO CORRESPOND WITH THE INCREASED
 PRESSURES FOR EXPOSURE D. FBC - R301.2.1
  
 3) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. (ENERGY CALCS.)
  
 4) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. SHOW THAT THE
 ENTIRE DWELLING WILL COMPLY.
  
 6) THE WOOD BEAM AND RAFTERS FOR THE PERGOLA THAT ARE
 EXPOSED TO THE WEATHER ARE REQUIRED TO BE PRESSURE
 TREATED OR OF APPROVED WOOD OF NATURAL DECAY
 RESISTANCE. R317.1.3 IN GEOGRAPHICAL AREAS WHERE
 EXPERIENCE HAS DEMONSTRATED A SPECIFIC NEED, APPROVED
 NATURALLY DURABLE OR PRESSURE-PRESERVATIVE-TREATED WOOD
 SHALL BE USED FOR THOSE PORTIONS OF WOOD MEMBERS THAT
 FORM THE STRUCTURAL SUPPORTS OF BUILDINGS, BALCONIES,
 PORCHES OR SIMILAR PERMANENT BUILDING APPURTENANCES
 WHEN THOSE MEMBERS ARE EXPOSED TO THE WEATHER WITHOUT
 ADEQUATE PROTECTION FROM A ROOF, EAVE, OVERHANG OR
 OTHER COVERING THAT WOULD PREVENT MOISTURE OR WATER
 ACCUMULATION ON THE SURFACE OR AT JOINTS BETWEEN
 MEMBERS.
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE SUBMITTALS
 FOR THE ASPHALT SHINGLE ROOFING.
  
 8) FBC R704 IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). THE
 STUCCO STOP IS REQUIRED TO BE 6 INCHES ABOVE FINAL
 EXTERIOR GRADE.
  
 9) THERE IS A CONFLICT BETWEEN THE BOTTOM PLATE ANCHORS
 FOR THE EXTERIOR WALLS ON SHEETS S-1 AND S-2. ON S-1
 THE ANCHORS SPECIFIED ARE 3/8" X 7-1/2" @ 24"O.C. AND
 3/4" X 6" @ 16" O.C. PLEASE CORRECT. FBC 107.2.1
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  