| 2014-09-23 16:47:26 | DATE: 9/23/2014 |
| | PROJECT: 221 PURITAN RD |
| | PERMIT#: 14090756 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) MINIMUM PLAN REVIEW CRIERIA REQUIRES A RISER |
| | DIAGRAM, PANEL SCHEDULE AND FLOOR PLAN DETAILING |
| | CIRCUIT NUMBERS AT EACH OUTLET, DEVICE AND EQUIPMENT |
| | LOCATIONS. WPB AMENDMENTS FBC 107.3.2 |
| | |
| | 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY |
| | ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF |
| | THE SERVICE CONDUCTORS. NEC 230.702) INDICATE |
| | RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET |
| | IN WIDTH HAVE A RECEPTACLE. NEC 210.52. |
| | |
| | 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 |
| | |
| | 4) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | 5) REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), |
| | 21011.C.3 |
| | |
| | 6) BATHROOM GFIC OUTLET PLANS FAIL TO INDICATE |
| | COMPLIANCE WITH SECTION 210.11 (C)(3) BATHROOM BRANCH |
| | CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS. |
| | |
| | 7) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |