| Plan Review Notes For Permit 14090742 |
| Permit Number |
14090742 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2014-10-16 10:50:22 | 10/16/2014 | | | PROJECT: 401 EXECUTIVE CNTR | | | PERMIT#: 14090742 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 4RD ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INVOLVED IN | | | THIS SCOPE OF WORK INDICATING THE CIRCUIT NUMBER, | | | AMPERE RATING AND VOLTAGE RATING FOR EACH CIRCUIT | | | INVOLVED IN THIS SCOPE OF WORK. | | | | | | 2) INDICATE THE CIRCUIT NUMBERS AND WIRE SIZES ON THE | | | SITE PLAN FOR EACH CIRCUIT INVOLVED IN THIS SCOPE OF | | | WORK. | | | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS | | | TO FBC 107.2.1 | | | | | | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | IS REQUIRED FOR THE FUTURE INSTALLATION OF SECURITY, | | | AND/OR CCTV. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|