Notes
Date Text
2014-10-10 10:27:2610/10/2014
 PROJECT: 401 EXECUTIVE CNTR
 PERMIT#: 14090742
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INVOLVED IN
 THIS SCOPE OF WORK INDICATING THE CIRCUIT NUMBER,
 AMPERE RATING AND VOLTAGE RATING FOR EACH CIRCUIT
 INVOLVED IN THIS SCOPE OF WORK.
  
 2) INDICATE THE CIRCUIT NUMBERS AND WIRE SIZES ON THE
 SITE PLAN FOR EACH CIRCUIT INVOLVED IN THIS SCOPE OF
 WORK.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR THE INSTALLATION OF SECURITY, AND/OR
 CCTV.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  