| Plan Review Notes For Permit 14090741 |
| Permit Number |
14090741 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-10 13:18:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A FLOOR PLAN WHICH SHOWS LOCATION OF WORK. | | | ALSO INCLUDE INFORMATION AS TO HOW IT HAS BEEN | | | DETERMINED THAT THE DOORS ARE NOT REQUIRED TO BE FIRE | | | RATED. NOT ENOUGH INFORMATION WAS PROVIDED FOR A | | | COMPLETE PLAN REVIEW FBC 107. | | | | | | 2. ON SHEET 11 OF THE DOOR NOA, INDICATE WHICH HARDWARE | | | IS PROPOSED, FBC 1008. | | | | | | 3. PROVIDE ENGINEERING FOR THE DESIGN PRESSURES | | | PROPOSED, FBC 1609. | | | | | | | | | | | | |
|