| | PROJECT: THE ALCHEMIST SIGN |
| | PERMIT#: 14090734 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: PASS WITH EXCEPTION. |
| | |
| | 1) PLEASE PROVIDE THE FOLLOWING FOR VERIFICATION BY |
| | ELECTRICAL INSPECTOR IN THE FIELD. |
| | A) FBC-E 505.2.4 |
| | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| | OF POWER FOR A MINIMUM OF 10 HOURS. |
| | B) NEC 600.3 |
| | ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| | FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| | OTHERWISE APPROVED BY SPECIAL PERMISSION. |
| | C) NEC 110.3(B) |
| | LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED |
| | IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE |
| | LISTING OR LABELING. |
| | D) NEC 600.5 |
| | EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| | A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |