Plan Review Notes
Plan Review Notes For Permit 14090724
Permit Number 14090724
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-09 15:39:0410/9/2014
 PROJECT: 625 GLENRIDGE DR.
 PERMIT#: 14090724
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) CLARIFY THE OVERALL SCOPE OF WORK. AND INDICATE ON
 THE FLOOR PLAN WHAT IS EXISTING TO REMAIN AND WHAT ID
 PROPOSED TO BE INSTALLED.
  
 2) PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE
 ELECTRICAL SERVICE AND A/C EQUIPMENT. WPB AMENDMENTS TO
 FBC 107.3.2
  
 3) INDICATE THE LOCATION OF THE ELECTRICAL PANEL ON THE
 FLOOR PLAN.
  
 4) PROVIDE A PANEL SCHEDULE INDICATING THE CIRCUIT
 NUMBERS CORESPONDING TO THE FLOOR PLAN.
  
 5) IDENTIFY THE CIRCUITRY ON THE FLOOR PLAN
 CORESPONDING TO THE ELECTRICAL PANEL.
  
 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.1, 406.11
  
 7) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC-107.2.1
  
 8) A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT
 THE FRONT AND BACK ENTRANCE AREAS. NEC 210.52 (E) (1)
  
 9) PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE
 BRANCH CIRCUITS. NEC 210.52
  
 10) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C).
  
 11) VERIFY THE EXISTING HOME ALSO HAS SMOKE DETECTORS
 AND CARBON MONOXIDE DETECTORS. REMODELING OF AN
 EXISTING STRUCTURE IS REQUIRED TO INCLUDE
 INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND OUTSIDE
 EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 12) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. NEC 210.11 (3)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved