| Plan Review Notes For Permit 14090724 |
| Permit Number |
14090724 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-09 11:53:45 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) FBC 107.2.1 THE PLANS THAT WERE SUBMITTED ARE NOT | | | CLEAR AS TO THE PROPOSED SCOPE OF WORK. SUBMIT TWO SETS | | | OF DRAWINGS THAT SHOW THE EXISTING CONDITION OF THE | | | PROJECT AREA PRIOR TO THE PROPOSED IMPROVEMENTS. | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE SUBMITTALS | | | FOR THE NEW WINDOWS AND EXTERIOR DOOR. THE SUBMITALS | | | FOR THE WINDOWS DO NOT HAVE THE FL# ON THEM AND NOTHING | | | WAS SUBMITTED FOR THE EXTERIOR DOOR. | | | | | | | | | |
|