| 2014-10-02 14:13:18 | BUILDING PLAN REVIEW |
| | PERMIT:14090715 |
| | ADD:325 EUCALYPTUS STREET |
| | CONT: KAST |
| | TEL: (561) 689-2910 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. OCT. 02/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE TEMPORARY |
| | CONSTRUCTION TRAILERS ARE TEMPORARY, THAT MEANS 180 |
| | DAYS OR LESS BY DEFINITON. PLEASE PROVIDE THE DATE THEY |
| | WILL BE INSTALLED AND THE DATE THEY WILL BE REMOVED. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 108.1 GENERAL. THE |
| | BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR |
| | TEMPORARY STRUCTURES AND TEMPORARY USES. SUCH PERMITS |
| | SHALL BE LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT |
| | BE PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR |
| | DEMONSTRATED CAUSE. |
| | |
| | 2) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE |
| | IN NOTE # 2 THEY WILL NEED TO PROVIDE STAIR, RAMP, |
| | LANDINGS, DECKS AND GAURDRAIL DETAILS, THEY ARE NOT |
| | INCLUDED IN THE STATE APPROVED PLANS. |
| | 2A) 1009.6 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL |
| | BE BUILT OF MATERIALS CONSISTENT WITH THE TYPES |
| | PERMITTED FOR THE TYPE OF CONSTRUCTION OF THE BUILDING, |
| | EXCEPT THAT WOOD HANDRAILS SHALL BE PERMITTED FOR ALL |
| | TYPES OF CONSTRUCTION. |
| | 2B) STAIR, RAMPS, LANDINGS & DECKS ARE TO BE DESIGN TO |
| | TABLE 1607 LIVE LOADS. |
| | 2C) 1010.2 SLOPE. RAMPS USED AS PART OF A MEANS OF |
| | EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN ONE |
| | UNIT VERTICAL IN 12 UNITS HORIZONTAL (8.333-PERCENT |
| | SLOPE). THE SLOPE OF OTHER PEDESTRIAN RAMPS SHALL NOT |
| | BE STEEPER THAN ONE UNIT VERTICAL IN EIGHT UNITS |
| | HORIZONTAL (12.5-PERCENT SLOPE). ACC CODE 405, |
| | HANDRAILS 1012 & GUARDRAILS 1013. |
| | |
| | 3) PROVIDE A SITE PLAN AND SHOW THE ACCESSIBLE ROUTE TO |
| | THE MANUFACTURERD BUILDINGS FROM THE ACCESSIBLE PARKINS |
| | SPOT AND ACCESS AISLE. |
| | 2010 FBC- ACCESS 502.1. |
| | |
| | 4) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE |
| | IN NOTE # 14 SITE INSTALLED ITEM GUTTERS. 1503.7 |
| | PROTECTION AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 5) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE |
| | IN NOTE # 16 STORM SHUTTERS. 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)((E) SHUTTERS. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |