| Plan Review Notes For Permit 14090701 |
| Permit Number |
14090701 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-08 09:46:07 | RESIDENTIAL (R2) FLOORING BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- WHISPERMAT-CS SOUND INSULATION MEMBRANE: | | | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE | | | DEVELOPED INDEX TEST IN ACCORDANCE WITH ASTM E 84 OR UL | | | 723 AS REQUIRED BY SEC. 719.1 OF 2010 FBC. | | | | | | B) INFORMATION SUBMITTED STATES THAT THE SOUND | | | TRANSMISSION CLASS (STC) AND THE IMPACT ISOLATION CLASS | | | (IIC) TEST WAS PERFORMED FOR AN 8" CONCRETE SLAB WITH A | | | SOUND RATED SUSPENDED CEILING. THIS IS NOT THE TYPE OF | | | FLOOR CEILING ASSEMBLY FOR THIS BUILDING. PROVIDE 2 | | | COPIES OF THE STC AND IIC TESTS THAT MATCH THE TYPE OF | | | ASSEMBLY IN THIS BUILDING TO SHOW COMPLIANCE WITH SEC. | | | 1207 OF FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|