| Date |
Text |
| 2014-12-22 11:01:38 | 12/22/2014 |
| | PROJECT: CHEATHAM RESIDENCE |
| | PERMIT#: 14090691 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A SYMBOLS AND FIXTURE LEGEND TO IDENTIFY ALL |
| | SYMBOLS ON THE PLAN. FBC-WPB AMENDMENTS 107.3.2 |
| | |
| | 2) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 3) PROVIDE THE CIRCUIT UMBRS ON THE FLOOR PLAN. FBC-WPB |
| | AMENDMENTS 107.3.2 |
| | |
| | 4) WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) |
| | OF THE OUTSIDE EDGE OF THE SINK. NEC 210.8 (5) |
| | |
| | 5) INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS |
| | INSTALLED NEW. |
| | |
| | 6) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE.NEC210.52(C)(1) |
| | |
| | 7) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED |
| | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. |
| | INDICATE REQUIRED SWITCHES AT STAIR LANDINGS. NEC |
| | 210.70(A) |
| | |
| | 8) AT LEAST ONE WALL SWITCH? CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE |
| | EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS. NEC |
| | 210.70(B) |
| | |
| | 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |