2014-12-22 06:37:39PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) SUBMIT TWO SETS OF REVISED STRUCTURAL PLANS THAT
 ACCURATELY REFLECT THE REVISED SCOPE OF WORK THAT IS
 SHOWN ON THE NEW ARCHITECTURAL DRAWINGS. FBC 107.2.1
  
 2) SPECIFY THE DIMENSIONS OF THE EXISTING DOORS AND
 WINDOWS IN THE SCHEDULE ON SHEET A6.1. FBC R301.2.1 AND
 R310
  
 3) PRODUCT APPROVALS WERE SUBMITTED FOR SINGLE HUNG AND
 HORIZONTAL SLIDING WINDOWS, HOWEVER, THERE ARE NOT ANY
 SHOWN IN THE WINDOW SCHEDULE. PLEASE CLARIFY. FBC
 107.2.1
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS AND AWNING WINDOWS IN WRITING BY
 THE DESIGNER OF RECORD. FBC 107.3.4
  
 5) THE PRODUCT APPROVALS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS ( NOA NO. 13-1024.05 ) AND THE CASEMENT WINDOWS
 ( NOA NO. 09-1105.03 ) HAVE BEEN SUPERSEDED. FBC
 107.3.4 - PROVIDE TWO SETS OF THE CURRENT PRODUCT
 APPROVALS FOR THESE ITEMS WHICH ARE REGULATED BY DCA
 RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  