| Plan Review Notes For Permit 14090691 |
| Permit Number |
14090691 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-12-22 06:37:39 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) SUBMIT TWO SETS OF REVISED STRUCTURAL PLANS THAT | | | ACCURATELY REFLECT THE REVISED SCOPE OF WORK THAT IS | | | SHOWN ON THE NEW ARCHITECTURAL DRAWINGS. FBC 107.2.1 | | | | | | 2) SPECIFY THE DIMENSIONS OF THE EXISTING DOORS AND | | | WINDOWS IN THE SCHEDULE ON SHEET A6.1. FBC R301.2.1 AND | | | R310 | | | | | | 3) PRODUCT APPROVALS WERE SUBMITTED FOR SINGLE HUNG AND | | | HORIZONTAL SLIDING WINDOWS, HOWEVER, THERE ARE NOT ANY | | | SHOWN IN THE WINDOW SCHEDULE. PLEASE CLARIFY. FBC | | | 107.2.1 | | | | | | 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR | | | STRUCTURAL MULLIONS AND AWNING WINDOWS IN WRITING BY | | | THE DESIGNER OF RECORD. FBC 107.3.4 | | | | | | 5) THE PRODUCT APPROVALS SUBMITTED FOR THE SINGLE HUNG | | | WINDOWS ( NOA NO. 13-1024.05 ) AND THE CASEMENT WINDOWS | | | ( NOA NO. 09-1105.03 ) HAVE BEEN SUPERSEDED. FBC | | | 107.3.4 - PROVIDE TWO SETS OF THE CURRENT PRODUCT | | | APPROVALS FOR THESE ITEMS WHICH ARE REGULATED BY DCA | | | RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. | | | | | | IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. | | | | | | | | | |
|