Plan Review Notes
Plan Review Notes For Permit 14090691
Permit Number 14090691
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-14 14:58:5410/14/2014
 PROJECT: CHEATHAM RESIDENCE
 PERMIT#: 14090691
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ELECTRICAL PLANS. NONE PROVIDED WITH
 SUBMITTAL PACKAGE AND YET IT IS EVIDENT FROM THE SCOPE
 OF WORK SHOWN THAT AN ELECTRICAL PERMIT IS REQUIRED.
 WPB AMENDMENTS TO FBC 107.3.2
  
 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 3) ADDITIONAL NOTES AND OR DEFICIENCIES MAY BE NOTED
 ONCE ACTUAL ELECTRICAL PLANS HAVE BEE SUBMITTED FOR
 REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  