| 2014-10-08 17:49:32 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | ELECTRICAL |
| | |
| | 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS |
| | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA |
| | BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS |
| | REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF |
| | WORK THAT WILL BE PREFORMED UNDER THIS PERMIT. BASED ON |
| | THE ELECTRICAL PLANS THAT WERE SUBMITTED, IT APPEARS |
| | THAT THERE WILL BE A SERVICE CHANGE AND THE DWELLING IS |
| | BEING RE-WIRED. PLEASE CLARIFY. |
| | |
| | 2) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 3) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET. |
| | |
| | 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. |
| | |
| | 5) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| | |
| | 6) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED. |
| | |
| | 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 8) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE. |
| | |
| | 9) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. |
| | |
| | 10) FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. |
| | |
| | 11) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE |
| | ELECTRICAL EQUIPMENT ON THE PLANS. |
| | |
| | 12) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLETS. |
| | |
| | 13) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP |
| | RECEPTACLES SHALL BE SUPPLIED BY NO FEWER THAN TWO |
| | SMALL APPLIANCE BRANCH CIRCUITS. |
| | |
| | 14) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT |
| | LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS |
| | REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR |
| | EXITS. |
| | |
| | 15) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| | PRESENT. |
| | |
| | 16) NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE |
| | AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR |
| | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| | LESS. |
| | |
| | 17) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| | BE PROVIDED. |
| | |
| | 18) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| | PLANS. |
| | |
| | 19) NEC 210.52 (E)(1) ? AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED |
| | NOT MORE THAN 6 ? FT. ABOVE GRADE SHALL BE INSTALLED AT |
| | THE FRONT AND BACK OF THE DWELLING. |
| | |
| | |
| | |