Plan Review Notes
Plan Review Notes For Permit 14090683
Permit Number 14090683
Review Stop E
Sequence Number 2
Notes
Date Text
2014-10-08 17:49:32PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 ELECTRICAL
  
 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS
 LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA
 BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF
 WORK THAT WILL BE PREFORMED UNDER THIS PERMIT. BASED ON
 THE ELECTRICAL PLANS THAT WERE SUBMITTED, IT APPEARS
 THAT THERE WILL BE A SERVICE CHANGE AND THE DWELLING IS
 BEING RE-WIRED. PLEASE CLARIFY.
  
 2) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET.
  
 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED.
  
 5) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 6) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED.
  
 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 8) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE.
  
 9) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 10) FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 11) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL EQUIPMENT ON THE PLANS.
  
 12) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 13) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP
 RECEPTACLES SHALL BE SUPPLIED BY NO FEWER THAN TWO
 SMALL APPLIANCE BRANCH CIRCUITS.
  
 14) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT
 LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS
 REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR
 EXITS.
  
 15) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT.
  
 16) NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE
 AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR
 PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR
 LESS.
  
 17) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 18) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE
 REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE
 PLANS.
  
 19) NEC 210.52 (E)(1) ? AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6 ? FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF THE DWELLING.
  
  
  