| 2014-10-08 17:46:12 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | BUILDING |
| | |
| | 1) FBC-R703.6.3 WHERE CEMENT PLASTER (STUCCO) IS TO BE |
| | APPLIED TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL |
| | BE TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER |
| | AND THE WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE |
| | PROVIDED BETWEEN THE WATER-RESISTIVE BARRIER AND THE |
| | CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE |
| | FOLLOWING: |
| | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER |
| | MATERIAL; OR |
| | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE WRAP; OR |
| | 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 2) FBC-R803.2.3.1 SHEATHING FASTENINGS. |
| | WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO |
| | ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON |
| | CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE |
| | FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING |
| | MINIMUM DIMENSIONS: |
| | 1. 0.113 INCH NOMINAL SHANK DIAMETER. |
| | 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER. |
| | 3. 16 TO 20 RINGS PER INCH. |
| | 4. 0.280 INCH FULL ROUND HEAD DIAMETER. |
| | 5. 2 INCH NAIL LENGTH. |
| | WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < |
| | 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE |
| | 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE WITH |
| | FIGURE R803.2.3.1 WHERE VASD AS DETERMINED IN |
| | ACCORDANCE WITH SECTION R301.2.1.3 IS 130 MPH OR |
| | GREATER. |
| | |
| | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 4) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT |
| | FOR THE ICYNENE SPRAY FOAM INSULATION. FBC R316 |
| | |
| | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE METAL ROOFING |
| | SUBMITTALS. |
| | |
| | 6) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | |
| | |
| | |
| | |