| 2014-10-08 18:43:42 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | MECHANICAL |
| | |
| | NOTE: MECHANICAL PLANS HAVE BEEN ADDED TO THIS |
| | SUBMITTAL THAT WERE NOT INCLUDED IN THE ORIGINAL PLANS |
| | THAT WERE SUBMITTED. |
| | |
| | 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS |
| | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA |
| | BUILDING CODE AND OTHER RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS AS REQUIRED BY FBC 107.2.1. |
| | CLEARLY SPECIFY THE SCOPE OF WORK THAT WILL BE |
| | PREFORMED UNDER THIS PERMIT. |
| | IS THIS AN EXISTING HVAC SYSTEM THAT IS BEING REPLACED, |
| | A NEW INSTALLATION OR JUST NEW DUCT WORK. |
| | |
| | 2) FBC - R M1401.3 SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| | |
| | 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND |
| | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN |
| | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT |
| | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. |
| | |
| | 4) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW |
| | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, |
| | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, |
| | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, |
| | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, |
| | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, |
| | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM |
| | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. |
| | |
| | NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL |
| | COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED. |