| 2014-10-03 16:00:09 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | ELECTRICAL |
| | |
| | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS |
| | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA |
| | BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS |
| | REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF |
| | WORK THAT WILL BE PREFORMED UNDER THIS PERMIT. |
| | |
| | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET. |
| | |
| | 5) NEC 210.8 (A) (1)-(8) - GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. |
| | |
| | 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| | |
| | 7) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED. |
| | |
| | 8) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 9) NEC 240.24(A) & (B) PANELS SHALL BE READILY |
| | ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. |
| | SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL |
| | FLOOR PLAN. |
| | |
| | 10) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE. |
| | |
| | NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL |
| | COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED. |