Plan Review Notes
Plan Review Notes For Permit 14090678
Permit Number 14090678
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-22 08:58:26NEW SIGN BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. REVISE VALUATION AS REQUIRED.
 PROVIDE COPY OF SIGN CONTRACT.
  
 2- ENGINEER OF RECORD TO CLEARLY IDENTIFY IF THE DESIGN
 WIND SPEED SPECIFIED IN THE WIND LOAD INFORMATION IS
 THE ULTIMATE DESIGN WIND SPEED OR THE NOMINAL DESIGN
 WIND SPEED. SEC. 1609.3 OF 2010 FBC-BUILDING. REVISE
 PLANS AS REQUIRED TO CLARIFY.
  
 3- ENGINEER OF RECORD TO CLARIFY SIZE OF ANCHORS TO BE
 USED. THERE ARE TWO DIFFERENT ANCHOR SIZES SPECIFIED ON
 PLANS SUBMITTED. FOR EXAMPLE SHEET SEC1 SPECIFIES 3/8"
 DIAMETER ANCHORS, WHILE SHEET W1 SPECIFIES 1/4"
 DIAMETER ANCHORS. REVISE ALL DRAWING S AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]