| 2014-10-22 08:58:26 | NEW SIGN BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN | | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | | AMENDMENTS TO FBC. REVISE VALUATION AS REQUIRED. | | | PROVIDE COPY OF SIGN CONTRACT. | | | | | | 2- ENGINEER OF RECORD TO CLEARLY IDENTIFY IF THE DESIGN | | | WIND SPEED SPECIFIED IN THE WIND LOAD INFORMATION IS | | | THE ULTIMATE DESIGN WIND SPEED OR THE NOMINAL DESIGN | | | WIND SPEED. SEC. 1609.3 OF 2010 FBC-BUILDING. REVISE | | | PLANS AS REQUIRED TO CLARIFY. | | | | | | 3- ENGINEER OF RECORD TO CLARIFY SIZE OF ANCHORS TO BE | | | USED. THERE ARE TWO DIFFERENT ANCHOR SIZES SPECIFIED ON | | | PLANS SUBMITTED. FOR EXAMPLE SHEET SEC1 SPECIFIES 3/8" | | | DIAMETER ANCHORS, WHILE SHEET W1 SPECIFIES 1/4" | | | DIAMETER ANCHORS. REVISE ALL DRAWING S AS REQUIRED TO | | | MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|