| Plan Review Notes For Permit 14090659 |
| Permit Number |
14090659 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-02-18 13:03:14 | PASS PROVISO | | | 1) REFER TO SECTION 301.12 WIND RESISTANCE. | | | 2010 FBC (M) PROVIDE A DETAIL FROM THE | | | ENGINEER ON THE CURB TO ROOF TIEDOWN. | | | SIZE AND TYPE OF ANCHORS USED | | | 2) REFER TO SECTION 503.2.5.4 SHUTOFF | | | DAMPER CONTROLS. FOR FRESH AIR | | | AND EXHAUST. 2010 FLORIDA ENERGY CODE | | | 3) HOODS AND COOLERS ARE NOT PART OF THIS REVIEW | | | SEPARATE APPLICATION, PLANS AND PERMITS ARE REQUIRED | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|