| Date |
Text |
| 2015-02-11 16:07:25 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | SHEET'S LS - 1 AND A - 1, COMPLIED |
| | |
| | ADDITIONAL: THE DOOR SCHEDULE ONLY LISTS THE FRONT EXIT |
| | DOOR AS BEING 12' WIDE, NO CLEAR OPENING DIMENSION IS |
| | INDICATED TO VERIFY THE EXIT CAPACITY. |
| | ONE ONE SHEET THERE ARE FOUR DOOR AND FOUR EXIT ARROWS |
| | SHOWING FROM THE FRONT FOYER AREA. ANOTHER SHEET SHEET |
| | SHOWS TWO. THE FOYER EXIT DESIGN IS NOT CONSISTENT |
| | AND NEEDS CORRECTION. REMAINS- PROVISO: WILL ADDRESS |
| | DURING CONSTRUCTION. |
| | |
| | SHEET'S LS - 1 AND A - 1, DOORS 16, 18, AND 22 ARE |
| | INDICATED AS EXITS. APPEARS TO BE COMPLIED; HOWEVER, |
| | PROVISO: WILL ADDRESS DURING CONSTRUCTION. |
| | |
| | ADDITIONAL : THE SUBMITTAL CONTINUES TO SHOW A FENCED |
| | IN AREA IN THE REAR OF THE BUILDING THAT THESE THREE |
| | EXIT DOORS OPEN UP TO. THERE DOES NOT SEEM TO BE AN |
| | EXIT OUT OF THIS |
| | FENCED IN AREA. IF THERE IS NO CLEAR EXIT FROM THIS |
| | AREA , THESE THREE DOORS CAN NOT BE USED AS EXIT DOORS |
| | AND YOUR EXIT CALCULATIONS NEED TO BE CORRECTED. |
| | APPEARS TO BE COMPLIED; HOWEVER, PROVISO : WILL ADDRESS |
| | DURING CONSTRUCTION. |
| | |
| | SHEET A - 5, THE DOOR SCHEDULE IS STAPLED IN SUCH A WAY |
| | THAT IT IS UNREADABLE AND DOORS CAN NOT BE LOCATED OR |
| | VERIFIED. COMPLIED |
| | |
| | ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND |
| | HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN |
| | THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS |
| | CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE |
| | EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR |
| | TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL |
| | BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR |
| | SCHEDULE. PROVISO: WILL ADDRESS DURING CONSTRUCTION. |
| | |
| | EMERGENCY LIGHTING IS NOT PROVIDED FOR OR INDICATED. |
| | COMPLIED |
| | |
| | |
| | ADDITIONAL EXIT SIGNS SHALL BE PLACED AT THE END OF |
| | MAIN ISLES AND AT THE OPPOSITE CORNERS OF THE MAIN |
| | SHOPPING AREA. (NOTE THE LOCATIONS ON SHEET LS - 1) |
| | ADDITIONAL SIGNS MAY BE ADDED IF OBSTRUCTED BY LINE OF |
| | SITE ISSUES DURING INSPECTIONS. PROVISO: WILL ADDRESS |
| | ANY ADDITIONAL NEEDED EXIT SIGNS DURING CONSTRUCTION. |
| | |
| | THE PROPOSED GENERATOR SHALL MEET THE REQUIREMENTS OF |
| | NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER |
| | SYSTEMS. THE GENERATOR SHALL BE PROTECTED FROM DAMAGE |
| | BY VEHICLE TRAFFIC. COMPLIED |
| | |
| | A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING |
| | FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN |
| | EMERGENCY AT ANY TIME. COMPLIED |
| | |
| | NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| | DOOR. PROVISO: WILL ADDRESS DURING CONSTRUCTION. |
| | |
| | ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH |
| | NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS |
| | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. COMPLIED |
| | |
| | A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS |
| | STRUCTURE. COMPLIED |
| | |