Plan Review Notes
Plan Review Notes For Permit 14090659
Permit Number 14090659
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2015-02-11 16:07:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 SHEET'S LS - 1 AND A - 1, COMPLIED
  
 ADDITIONAL: THE DOOR SCHEDULE ONLY LISTS THE FRONT EXIT
 DOOR AS BEING 12' WIDE, NO CLEAR OPENING DIMENSION IS
 INDICATED TO VERIFY THE EXIT CAPACITY.
 ONE ONE SHEET THERE ARE FOUR DOOR AND FOUR EXIT ARROWS
 SHOWING FROM THE FRONT FOYER AREA. ANOTHER SHEET SHEET
 SHOWS TWO. THE FOYER EXIT DESIGN IS NOT CONSISTENT
 AND NEEDS CORRECTION. REMAINS- PROVISO: WILL ADDRESS
 DURING CONSTRUCTION.
  
 SHEET'S LS - 1 AND A - 1, DOORS 16, 18, AND 22 ARE
 INDICATED AS EXITS. APPEARS TO BE COMPLIED; HOWEVER,
 PROVISO: WILL ADDRESS DURING CONSTRUCTION.
  
 ADDITIONAL : THE SUBMITTAL CONTINUES TO SHOW A FENCED
 IN AREA IN THE REAR OF THE BUILDING THAT THESE THREE
 EXIT DOORS OPEN UP TO. THERE DOES NOT SEEM TO BE AN
 EXIT OUT OF THIS
 FENCED IN AREA. IF THERE IS NO CLEAR EXIT FROM THIS
 AREA , THESE THREE DOORS CAN NOT BE USED AS EXIT DOORS
 AND YOUR EXIT CALCULATIONS NEED TO BE CORRECTED.
 APPEARS TO BE COMPLIED; HOWEVER, PROVISO : WILL ADDRESS
 DURING CONSTRUCTION.
  
 SHEET A - 5, THE DOOR SCHEDULE IS STAPLED IN SUCH A WAY
 THAT IT IS UNREADABLE AND DOORS CAN NOT BE LOCATED OR
 VERIFIED. COMPLIED
  
 ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE. PROVISO: WILL ADDRESS DURING CONSTRUCTION.
  
 EMERGENCY LIGHTING IS NOT PROVIDED FOR OR INDICATED.
 COMPLIED
  
  
 ADDITIONAL EXIT SIGNS SHALL BE PLACED AT THE END OF
 MAIN ISLES AND AT THE OPPOSITE CORNERS OF THE MAIN
 SHOPPING AREA. (NOTE THE LOCATIONS ON SHEET LS - 1)
 ADDITIONAL SIGNS MAY BE ADDED IF OBSTRUCTED BY LINE OF
 SITE ISSUES DURING INSPECTIONS. PROVISO: WILL ADDRESS
 ANY ADDITIONAL NEEDED EXIT SIGNS DURING CONSTRUCTION.
  
 THE PROPOSED GENERATOR SHALL MEET THE REQUIREMENTS OF
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS. THE GENERATOR SHALL BE PROTECTED FROM DAMAGE
 BY VEHICLE TRAFFIC. COMPLIED
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME. COMPLIED
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR. PROVISO: WILL ADDRESS DURING CONSTRUCTION.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. COMPLIED
  
 A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. COMPLIED
  