| 2015-02-04 11:38:32 | BUILDING PLAN REVIEW |
| | PERMIT: 14090659 |
| | ADD: 500 BELVEDERE RD |
| | CONT: OAK CONSTRUCTION |
| | TEL:(954)583-9625 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: SAT. FEB. 28/2015 |
| | ACTION: |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | |
| | 3) COMPLIED. SOILS REPORTS. |
| | |
| | 4-13) BUILDING PROVISO; |
| | |
| | 5-13) 107.3.4.2 DEFERRED SUBMITTALS: 107.3.4.2 FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE (PUBLIX) WHO SHALL REVIEW THEM AND |
| | FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP |
| | INSULATION |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS, A/C ROOF CURBS AND ADAPTORS |
| | |
| | 14)(A-C) COMPLIED. |
| | |
| | . |
| | |
| | 14C) . REVISION REQUIRED. THE DOOR SCHEDULE HAS BEEN |
| | MOVED SO THE DOOR IDENTIFICATION NUMBERS ARE VISIBLE. |
| | THE REMAINING ISSUE IS THE DOOR HARDWARE SHOWS HARDWARE |
| | TYPE GROUPS BUT THERE IS NO HARDWARE SCHEDULE SHOWN ON |
| | THIS PAGE. COMPLIANCE WITH DOOR TYPE AND REQUIED |
| | HARDWARE CAN NOT BE VERIFIED. RESPONCE INDICATES SEE |
| | SHEET PM-5. SHEET PM 4-5 BOTH SHOW THE HARDWARE SPECS, |
| | NOT A HARDWARE SCHEDULE. A REVISION WILL BE REQUIRED |
| | WITH A HARDWARE SCHEDULE, REVIEWED AND APPROVED BY THE |
| | BUILDING DEPARTMENT BEFORE THE FRAMING INSPECTION. |
| | |
| | 14D-E) COMPIED. |
| | |
| | 15) SEMI-COMPLIED. SHEET LS-1 VESTIBULE THE PLANS SHOW |
| | A NEW LOCATION FOR 2 ELECTRIC CARTS. THE LOCATION AS |
| | SHOWN ON THE PLANS IS NOT CLEAR IF THE 30 X 48 INCH |
| | CLEAR FLOOR SPACE IS MAINTAINED IN THE 2 ELECTRIC CART |
| | LOCATIONS. SHEET LS-1 AND EQ-1 ARE REVISED, SHEET EQ |
| | HAS A OTE CART STOP SEE A-1 FOR DETAILS BUT THERE IS NO |
| | DETAIL SHOWING THE ELECTRIC CART BUT A DETAIL OF THE |
| | FINISHED CORNER. |
| | |
| | 16-17) COMPLIED. |
| | |
| | 17) |
| | |
| | 18A-B) 4TH REVIEW.DETERMINING THE WIND DESIGN CRITERIA |
| | FOR COMPONENTS & CLADDING AND ASSOCIATED PRESSURES. |
| | SHEET A-1 DESIGN PRESSURES ARE AS REQUESTED IN VASD. |
| | THE DESIGN CRITERIA THE DESIGNER OF RECORD HAS USED IS |
| | ASCE 7-10 TABLE 28.3-1. THIS TABLE IS TO BE USED IN |
| | CONJUNCTION WITH THE MWFRS, MAIN WIND FORCE RESISTING |
| | SYSTEM. WITHIN THIS TABLE THE MULTIPLIER OF 1.16 IS FOR |
| | A EXPOSURE D. |
| | |
| | PLEASE REFER BACK TO CHAPTER 26 WIND LOADS : GENERAL |
| | REQUIREMENTS 26.1.2.1 MAIN WIND FORCE RESISTING SYSTEM |
| | (2) IS FOR THE ENVELOPE REQUIREMENTS OF A BUILDING SUCH |
| | AS BAR JOIST SYSTEMS. FOR DETERMINING MWFRS YOU USE |
| | TABLE 28.2-1 STEP 4 DETERMINING VELOCITY PRESSURE |
| | EXPOSURE COEFFICIENT, K2 OR KH, SEE TABLE 28.3-1. |
| | |
| | SECTION 26.1.2.2 DEALS WITH COMPONENTS & CLADDING. ALSO |
| | SEE 26.7.4.2 ENVELOPE PRESSURES CHAPTER 28 FOR THE |
| | MWFRS. 26.7.4.4. |
| | COMPONENTS AND CLADDING ARE DESIGNED UNDER CHAPTER 30 |
| | COMPONENTS AND CLADDING ARE BASED ON THE EXPOSURE |
| | CATEGORY RESULTING IN THE HIGHEST WIND LOADS FOR ANY |
| | WIND DIRECTION AT THE SITE. PLEASE REFER TO TABLE |
| | 30.4.1 OR TABLE 30.5-1 (SIMLIFIED METHOD) STEPS TO |
| | DETERMINE FOR THE STEPS TO DETERMINE COMPONENTS & |
| | CLADDING WIND LOADS FOR ENCLOSED LOW -RISE BUILDINGS. |
| | |
| | 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES |
| | FOR THE ROOF ZONE. THIS COMMENT WAS MEANT FOR ROOF |
| | ZONES FOR COMPONENTS AND CLADDING. SHEET S-7 THE DECK/ |
| | ROOFING UPLIFT PLAN IS IN VULT. IS THIS FOR THE ACTUAL |
| | ROOF DECK? AND NOT THE ROOF COVERING, UNDER THE 4TH |
| | REVIEW THERE ARE NOW VASD PRESSURES FOR ROOF JOIST |
| | ASWELL FOR COMPONENTS AND CLADDING. |
| | MCG SHEET S.001 PROVIDES BOTH WALL AND ROOF PRESSURES |
| | FOR ZONES 1-5 THIS PLAN TAKES PRESSURES SUPPOSED AT 38 |
| | FEET. THERE IS A LOWER ROOF WITH A 3 FT. PARAPET. ROOF |
| | ZONE 3 FOR THE LOWER ROOF SHOULD HAVE THE SAME |
| | PRESSURES AS FOR ZONE 2 FOR A MENA ROOF HEIGHT OF |
| | APPROX. 29 FT. THERE WILL STILL NEED PRESSURES A ZONE 3 |
| | FOR THE HIGHER PORTION OF ROOF SEE MCG SHEETS A304 & |
| | A305 ELEVATIONS OF 36FT-8 IN AND 38 FT. I SPOKE WITH |
| | THE DESIGNERS OF USING THE 30 FT ELEVATION FOR THE |
| | LOWER ROOF AND WALL PRESSURES AND A SEPARATE HEADING |
| | FOR ROOF ZONE 3 AT ELEVATION 38 FT AND THE ASSOCIATED |
| | HIGHER PRESSURES. |
| | |
| | 19-26) COMPLIED. |
| | . |
| | |
| | 27) DEFERRED SUBMITAL PRESSURES PROVIDE FOR INSULATION |
| | SHEETS . ROOF TOP INSULATION TO BE A DEFERRED |
| | SUBMITTAL. |
| | |
| | 28) NO ACTION NEEDS TO BE TAKEN JUST A WORD OF |
| | CAUTION!L SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING |
| | ON THE ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST |
| | AND OR THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE |
| | ONCE THE ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2 |
| | FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| | SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. THE ISSUE IS NOT PRESSURES |
| | AS MUCH AS ALLOWABLE SPANS THAT WILL SHOW UP UNDER THE |
| | ROOFING APPROVAL. |
| | |
| | |
| | 29 )BUILDING PROVISO, DEFERRED SUBMITTAL. ATAS WIND |
| | LOCK SUFFIT PANELSWERE SUBMITTED THE FL COVERSHEET WAS |
| | NOT INCLUDED IDENTIFYING THE PRODUCT. THE STRUCTURAL |
| | SHEETS DO NOT PROVIDE THE NEGATIVE PRESSUES FOR THE |
| | SOFFIT. SEE SHEET A502 DETAIL # 01. PRODUCT APPROVAL: |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. |
| | |
| | 30) BUILDING PROVISO: ALL DEFERRED SUBMITTALS TO BE |
| | REVIEWED BY PUBLIX THE DESIGNER OF RECORD.2010 FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE (DESIGNER OF RECORD) PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 31) COMPLIED. |
| | |
| | 32) DEFERRED SUBMITTAL: DEALS WITH THE USE OF EFIS TYPE |
| | SYSTEMS. RESPONSE INDICATES 3 SETS OF PRODUCT APPROVAL |
| | BEING SUBMITTED, COMMENTS 5-13 THE DESIGNER OF RECORD |
| | "PUBLIX" HAS ELECTED TO HAVE THE PRODUCT APPROVALS BE A |
| | DEFFERED SUBMITAL. PLEASE NOTE THE RESPONSE INDICATES A |
| | SHEET T001, I'VE NOT FOUND THIS SHEET IN EITHER THE |
| | PUBLIX NOR MCG PLANS. THE RESPONSE ALSO INDICATES THAT |
| | THERE WAS A E-MAIL RESPONSE. WHEN THE DEFERRED |
| | SUBMITTAL IS SUBMITTED, THE MANUFACTURERS INSTALATION |
| | BOOKLET (3) WILL BE REQUIRED, (1) FOR RECORD RETENTION, |
| | (1) FOR THE RESIDENT INSPECTOR AND (1) SET FOR THE |
| | CONTRACTOR AND MEP INSPECTORS. |
| | |
| | 33) SEMI- COMPLIED. SHEET S001 OF THE MCG DRAWINGS LIST |
| | THE WIND DESIGN AS 170 VULT AND 132 VASD, THEN LIST THE |
| | PRESSURES FOR ALL ZONES BOTH POSITIVE AND NEGATIVE, IN |
| | VASD SEE COMMENT 18C. |
| | |
| | 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |