Notes
Date Text
2014-12-17 06:59:391) PLUMBING PLANS REFER TO CIVIL DRAWINGS AND SITE PLAN
 FOR CONTINUATION OF PLUMBING LINES. SITE PLANS AND
 CIVIL DRAWINGS HAVE NOTE BEEN SUBMITTED WITH THESE
 PLANS. SUBMIT 2 COPIES OF SITE PLANS AND CIVIL
 DRAWINGS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.2ND
 REQUEST.
 2) SHT. A-9 SHOWS THE STANDARD TOILET STALL AS 5 FT. IN
 LENGTH AND SHT.ADA-1 SHOWS THE LENGTH AS 6 FT. 2 INCHES
 IN LENGTH. CLARIFY.
 3) SHT. EQ-1 SUBMIT DETAILS FOR THE GREASE CONTAINER
 REFERENCED BETWEEN GRID LINES #9 & #10. SUBMIT DETAILS
 FOR FASTENING, ETC. ONLY ONE SHEET FOR THIS CONTAINER
 HAS BEEN SUBMITTED AND IT IS BASICALLY A COVER SHEET
 THAT GIVES VERY LITTLE INFORMATION.WPB AMEND.TO 2010
 FBC SEC. 107.2.1.
 4) THE DRINKING FOUNTAINS SHOWN ON THE MEZZANINE LEVEL
 SHALL BE AVAILABLE TO THE PUBLIC FOR USE. IF THE UNITS
 ON THE MEZZANINE LEVEL ARE FOR EMPLOYEES THEN UNITS
 SHALL BE LOCATED ON THE FIRST FLOOR FOR THE PUBLIC.
 THERE SHALL BE A MINIMUM OF TWO DRINKING FOUNTAINS
 SHALL BE REQUIRED PER THE 2010 FL. ACCESSIBILITY CODE
 SEC. 211.1. THE RESPONSE REFERRING TO THE DELI COUNTER
 SODA FOUNTAIN DISPENSING WATER IS INADEQUATE AND DOES
 NOT COMPLY WITH THE ACCESSIBILITY CODE.
 5) THE LETTER FROM THOMAS ENGINEERING BY BRANDON ULMER
 SHALL BEAR A WET SIGNATURE IN ACCORDANCE WITH FL.
 ADMIN. CODE RULE 61G15-23.002.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  