| 2014-12-17 06:59:39 | 1) PLUMBING PLANS REFER TO CIVIL DRAWINGS AND SITE PLAN |
| | FOR CONTINUATION OF PLUMBING LINES. SITE PLANS AND |
| | CIVIL DRAWINGS HAVE NOTE BEEN SUBMITTED WITH THESE |
| | PLANS. SUBMIT 2 COPIES OF SITE PLANS AND CIVIL |
| | DRAWINGS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.2ND |
| | REQUEST. |
| | 2) SHT. A-9 SHOWS THE STANDARD TOILET STALL AS 5 FT. IN |
| | LENGTH AND SHT.ADA-1 SHOWS THE LENGTH AS 6 FT. 2 INCHES |
| | IN LENGTH. CLARIFY. |
| | 3) SHT. EQ-1 SUBMIT DETAILS FOR THE GREASE CONTAINER |
| | REFERENCED BETWEEN GRID LINES #9 & #10. SUBMIT DETAILS |
| | FOR FASTENING, ETC. ONLY ONE SHEET FOR THIS CONTAINER |
| | HAS BEEN SUBMITTED AND IT IS BASICALLY A COVER SHEET |
| | THAT GIVES VERY LITTLE INFORMATION.WPB AMEND.TO 2010 |
| | FBC SEC. 107.2.1. |
| | 4) THE DRINKING FOUNTAINS SHOWN ON THE MEZZANINE LEVEL |
| | SHALL BE AVAILABLE TO THE PUBLIC FOR USE. IF THE UNITS |
| | ON THE MEZZANINE LEVEL ARE FOR EMPLOYEES THEN UNITS |
| | SHALL BE LOCATED ON THE FIRST FLOOR FOR THE PUBLIC. |
| | THERE SHALL BE A MINIMUM OF TWO DRINKING FOUNTAINS |
| | SHALL BE REQUIRED PER THE 2010 FL. ACCESSIBILITY CODE |
| | SEC. 211.1. THE RESPONSE REFERRING TO THE DELI COUNTER |
| | SODA FOUNTAIN DISPENSING WATER IS INADEQUATE AND DOES |
| | NOT COMPLY WITH THE ACCESSIBILITY CODE. |
| | 5) THE LETTER FROM THOMAS ENGINEERING BY BRANDON ULMER |
| | SHALL BEAR A WET SIGNATURE IN ACCORDANCE WITH FL. |
| | ADMIN. CODE RULE 61G15-23.002. |
| | |