| Plan Review Notes For Permit 14090659 |
| Permit Number |
14090659 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-01-03 09:12:08 | PLAN DENIED | | | 1) MISSING FIRE DAMPER IN ROOM 112 ELEC. EQUIP. | | | ROOM . REFER TO SECTION 607.5.3 FBC (M) 2010 | | | 2) PLEASE MARK RATED WALLS ON MECHANICAL PLAN | | | PER SECTION 107 FBC 2010 | | | 3) MARK OR NUMBER ROOMS ON MECHANICAL PLAN. | | | PER SECTION 107 FBC 2010 | | | 4) REFER TO SECTION 304.11 GUARDS FBC (M) 2010 | | | 5) REFER TO SECTION 1509.7 AND TABLE 1509.7 FBC 2010 | | | 6) HOODS AND COOLERS WILL NOT BE REVIEWED UNDER THIS | | | PERMIT NUMBER | | | SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | 2014-12-04 14:02:25 | NEW SHEETS SUBMITTED. JG. |
|