2015-01-03 09:12:08PLAN DENIED
 1) MISSING FIRE DAMPER IN ROOM 112 ELEC. EQUIP.
 ROOM . REFER TO SECTION 607.5.3 FBC (M) 2010
 2) PLEASE MARK RATED WALLS ON MECHANICAL PLAN
 PER SECTION 107 FBC 2010
 3) MARK OR NUMBER ROOMS ON MECHANICAL PLAN.
 PER SECTION 107 FBC 2010
 4) REFER TO SECTION 304.11 GUARDS FBC (M) 2010
 5) REFER TO SECTION 1509.7 AND TABLE 1509.7 FBC 2010
 6) HOODS AND COOLERS WILL NOT BE REVIEWED UNDER THIS
 PERMIT NUMBER
 SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED.
  