| 2014-12-18 11:06:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE FOLLOWING PREVIOUS COMMENTS DID NOT APPEAR TO BE |
| | ADDRESSED IN THIS RESUBMITTAL WITH ADDITIONAL |
| | INFORMATION. |
| | |
| | |
| | SHEET'S LS - 1 AND A - 1, THE FRONT DOOR DIMENSIONS |
| | COULD NOT BE VERIFIED TO ACCOUNT FOR THE OCCUPANCY EXIT |
| | LOADS. IT APPEARS THAT 1/2 OF THE OCCUPANY CAN NOT EXIT |
| | THROUGH THE FRONT DOORS. PLEASE PROVIDE GREATER DETAIL |
| | OF THE OPENING DIMENSIONS AND CALCULATIONS. |
| | |
| | ADDITIONAL: THE DOOR SCHEDULE ONLY LISTS THE FRONT EXIT |
| | DOOR AS BEING 12' WIDE, NO CLEAR OPENING DIMENSION IS |
| | INDICATED TO VERIFY THE EXIT CAPACITY. |
| | ONE ONE SHEET THERE ARE FOUR DOOR AND FOUR EXIT ARROWS |
| | SHOWING FROM THE FRONT FOYER AREA. ANOTHER SHEET SHEET |
| | SHOWS TWO. THE FOYER EXIT DESIGN IS NOT CONSISTENT |
| | AND NEEDS CORRECTION. |
| | |
| | SHEET'S LS - 1 AND A - 1, DOORS 16, 18, AND 22 ARE |
| | INDICATED AS EXITS. THERE APPEARS TO BE A CHAIN LINK |
| | FENCE AREA THAT THESE DOORS EXIT DISCHARGE TO. THE EXIT |
| | DISCHARGE SHALL BE TO A UNOBSTRUCTED PUBLIC WAY. |
| | |
| | ADDITIONAL : THE SUBMITTAL CONTINUES TO SHOW A FENCED |
| | IN AREA IN THE REAR OF THE BUILDING THAT THESE THREE |
| | EXIT DOORS OPEN UP TO. THERE DOES NOT SEEM TO BE AN |
| | EXIT OUT OF THIS |
| | FENCED IN AREA. IF THERE IS NO CLEAR EXIT FROM THIS |
| | AREA , THESE THREE DOORS CAN NOT BE USED AS EXIT DOORS |
| | AND YOUR EXIT CALCULATIONS NEED TO BE CORRECTED. |
| | |
| | SHEET A - 5, THE DOOR SCHEDULE IS STAPLED IN SUCH A WAY |
| | THAT IT IS UNREADABLE AND DOORS CAN NOT BE LOCATED OR |
| | VERIFIED. |
| | |
| | ADDITIONAL : THE STAPLES MUST BE MOVED TO ALLOW FOR |
| | EASY VIEWING OF ALL DRAWINGS AND TABLES. |
| | |
| | ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND |
| | HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN |
| | THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS |
| | CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE |
| | EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR |
| | TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL |
| | BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR |
| | SCHEDULE. |
| | |
| | EMERGENCY LIGHTING IS NOT PROVIDED FOR OR INDICATED. |
| | |
| | ADDITIONAL : A STATEMENT, NOTE OR SYMBOL REGARDING |
| | EMERGENCY LIGHTING SHALL BE INDICATED ON THE LIFE |
| | SAFETY AND ELECTRICAL PLAN. |
| | |
| | ADDITIONAL EXIT SIGNS SHALL BE PLACED AT THE END OF |
| | MAIN ISLES AND AT THE OPPOSITE CORNERS OF THE MAIN |
| | SHOPPING AREA. (NOTE THE LOCATIONS ON SHEET LS - 1) |
| | ADDITIONAL SIGNS MAY BE ADDED IF OBSTRUCTED BY LINE OF |
| | SITE ISSUES DURING INSPECTIONS. |
| | |
| | ADDITIONAL : ANY PERSON STANDING ON ANY MAIN ISLE SHALL |
| | BE ABLE TO SEE AN EMERGENCY LIGHT. |
| | |
| | THE PROPOSED GENERATOR SHALL MEET THE REQUIREMENTS OF |
| | NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER |
| | SYSTEMS. THE GENERATOR SHALL BE PROTECTED FROM DAMAGE |
| | BY VEHICLE TRAFFIC. |
| | |
| | ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE |
| | APPROPRIATE. |
| | |
| | THE ELEVATOR SHALL CONFORM TO THE REQUIREMENTS TO THE |
| | FIREFIGHTERS EMERGENCY OPERATIONS AND ACCOMODATE THE |
| | EMS STANDARDS FOR STRETCHER DIMENSIONS. |
| | |
| | ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE |
| | APPROPRIATE. |
| | |
| | A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING |
| | FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN |
| | EMERGENCY AT ANY TIME. |
| | |
| | ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE |
| | APPROPRIATE. |
| | |
| | NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| | DOOR. |
| | |
| | ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE |
| | APPROPRIATE. |
| | |
| | ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH |
| | NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS |
| | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. |
| | |
| | ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE |
| | APPROPRIATE. |
| | |
| | A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS |
| | STRUCTURE. |
| | |
| | ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE |
| | APPROPRIATE. |
| | |
| | |
| | |
| | |