Plan Review Notes
Plan Review Notes For Permit 14090659
Permit Number 14090659
Review Stop P
Sequence Number 1
Notes
Date Text
2014-10-15 14:26:031) PLANS SUBMITTED SHOW TWO DIFFERENT SETS OF PLANS-ONE
 HAS HEADING OF SUPPLEMENTAL DRAWINGS BUT ARE FROM A
 DIFFERENT ARCHITECT. PROVIDE COMPLIANCE W/ FL, ADMIN.
 CODE RULE 61G1-23.015.
 2) THE PLANS FROM PUBLIX DESIGN DEPARTMENT REFER TO
 CIVIL DRAWINGS BUT THERE ARE NO CIVIL DRAWINGS IN THE
 SET OF PLANS. SUBMIT A COMPLETE SET OF CIVIL DRAWINGS
 FOR REVIEW.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) SHOW THE SQUARE FOOTAGE OF THE CANOPY THAT IS
 DRAINED BY THE 10" X 5" GUTTERS.
 4) SHT. P100 - SUMP PUMP DETAIL - NOTES" REFER TO SLAB
 UNDER DRAINDRAIN DETAIL." THERE IS NO DRAIN DETAIL.
 CLARIFY.
 5) A UNISEX TOILET ROOM IS REQUIRED PER TABLE 403.1
 FOOTNOTE "G" AND 2010 FPC SEC.403.5.
 6) SHT. EQ-1 - SUBMIT DETAILS FOR THE GREASE CONTAINER
 REFERENCED BETWEEN GRID LINES #9 & #10. WPB AMEND. TO
 2010FBC SEC. 107.2.1.
 7) SHT. A-2 - THE SINK IN THE LOUNGE SHALL COMPLY WITH
 THE FL. ACCESSIBILITY CODE SEC.212.
 8) SHT. A-8 - SOME OF THE PLUMBING VENTS APPEAR TO BE
 WITHIN 10 FT. OF AIR INTAKE OPENINGS ON THE ROOF..
 COMPLY W/ FPC SEC.904.5. PLACE A NOTE ON THE PLAN
 STATING THAT THE PLUMBING VENTS THROUGH THE ROOF WILL
 COMPLY W/ SEC.904.5 OF THE FPC.
 9) SHT. A-8 - SOME OF THE INFO & EQUIPMENT APPEARS TO
 BE CUT OFF/ MISSING FROM THE ROOF PLAN. CLARIFY.
 10) SHT A-9 -TOILET ACCESSORY LEGEND - ITEM R18 REFERS
 TO VERTICAL GRAB BAR- GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION PER THE FACBC SEC.609.4.
 11) SHT.A-9 - SHOWS THE STANDARD TOILET STALL IN THE
 WOMEN'S RESTROOM AS 34 1/8 INCHES WIDE AND 5 FT. IN
 LENGTH AND SHT. ADA-1 SHOWS THE STALL AS 3 FT. WIDE AND
 6 FT.2 INCHES IN LENGTH. CLARIFY.
 12) SHT.P-1 - DRAWING NOTES - #30 - STATES THE GAS LINE
 TO THE STANDBY GENERATOR TO BE 1 1/2 " BUT THE PLAAN
 APPEARS TO SHOW 2". CLARIFY.
 13) SHT. P-1- PLUMBING DESIGN DATA - EMERGENCY
 GENERATOR GAS LINE SIZING - SHOWS THE PIPE LENGTHAS 20
 FT.BUT 12 FT. IS USED IN THE EQUATION. CLARIFY.
 14) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE
 GENERATORS. GENERATORS SHALL COMPLY WITH NFPA 37 AND
 MEET THE REQUIREMENTS OF UL 2200. WPB AMEND. TO 2010
 FBC SEC.,107.2.1.
 15) SHT.P-2 - FIXTURE P-23 IS SHOWN ON THE FLOOR PLAN
 BUT NOT ON THE RISER DIAGRAM.
 16) SHT. P-2 - FIXTURE P-18 IS SHOWN ON SHT.P-1 BUT NOT
 ON THE RISER ON SHT. P-2.
 17) SUBMIT MANUF. SPEC SHEETS FOR THE STANCOR OIL
 MINDER PUMP. WPB AMEND.TO 2010 FBC SEC.107.2.1.
 18) SHT. P-3 - SHOWS CONDENSATE DRAINING INTO THE
 GREASY WASTE SYSTEM. WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY SEPARATOR OR INTERCEPTOR. 2010 FPC SEC.1003.2. SEE
 CONDENSATES IN MEAT & DELI DEPARTMENTS.
 19) SHT.P-4 - GROUND FLOOR BATHROOMS SHOWS THE
 CLEANOUTS FOR THE STACKS TURNED INTO THE MEAT COOLER.
 IS THIS CORRECT? CLARIFY.
 20) SHT. P-4 - THE VENT FROM THE FIRST FLOOR RESTROOMS
 IS 3" THEN REDUCES TO 2" AT THE VENT CONNECTION W/
 FIXTURE P-5.CLARIFY.
 21) SHT. P-4 - THE VENT FROM FIXTURE P-5 IN THE WOMEN'S
 RESTROOM IS SHOWN AS 2" THEN INCREASES TO 3". CLARIFY.
 22) SHT. P-4 - SIZE THE DRAIN LINE FOR FIXTURE P-5 IN
 THE MEN'S RESTROOM.
 23) SHT.P-4 - SHOWS THE CONDENSATE FROM AH-2 DRAINING
 INTO THE GREASY WASTE. WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY SEPARATOR OR INTERCEPTOR. 2010 FPC SEC.1003.2.
 24) SHT. P-6 - DETAIL #5 - THE DESIGN OF THE
 INTERCEPTOR DOES NOT COMPLY W/ SEC.1003.5.2 OF THE 2010
 FPC. THE INLET INVERT SHALL DISCHARGE A MINIMUM OF 2
 1/2 " ABOVE THE LIQUID LEVEL LINE AND THE INLET AND
 OUTLET PIPING SHALL BE A MIN. OF 4" IN DIAMETER.
 25) THE DRINKING FOUNTAINS SHALL BE AVAILABLE TO PUBLIC
 FOR USE. A MINIMUM OF 2 DRINKING FOUNTAINS SHALL BE
 INSTALLED ON THE FIRST FLOOR FOR CUSTOMERS IN
 ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE
 SEC.211.2
 26) SHT. P-3 - GREASE INTERCEPTOR SIZING - THE SIZING
 CRITERIA SHOWN ON THE PLANS IS FOR HYDRO-MECHANICAL
 TYPE INTERCEPTORS. DETAIL #5 ON SHT.P-6 SHOWS A
 CONCRETE VAULT GRAVITY INTERCEPTOR. YOU CANNOT USE THE
 CRITERIA FOR A HYDRO-MECHANICAL UNIT TO SIZE A GRAVITY
 TYPE INTERCEPTOR. THE FORMULAS IN TABLE 1003.5.1 MUST
 BE USED FOR THE GRAVITY INTERCEPTOR. REFER TO 2010 FPC
 SEC.1003.5.1.