Plan Review Notes
Plan Review Notes For Permit 14090659
Permit Number 14090659
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-30 11:21:01BUILDING PLAN REVIEW
 PERMIT: 14090659
 ADD: 500 BELVEDERE RD
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 30/ 2014
 ACTION: DENIED
  
 NOTE! PLANS INDICATE THEY ARE ONLY 50% COMPLETE. A
 THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 1) THE PLANS SUBMITED SHOW TWO DIFFERENT SETS OF PLANS
 ,ONE HAS THE HEADING OF SUPPLEMENTAL DRAWINGS, BUT THEY
 ARE FROM A DIFFERENT ACHITECT, AND FIRM. PLEASE PROVIDE
 COMPLIANCE WITH FL. ADMINISTRATIVE CODE, 61G1-23.015
 RESPONSIBLE SUPERVISING CONTROL OVER ARCHITECTURAL
 PRACTICE OUTSIDE OF THE ARCHITECT'S OFFICE.
  
  
  
 2A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY.
 THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR FOR:
 BUILDING TYPE II CONSTRUCTION
 FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT
 FOR ALL MAJOR STRUCTURAL ALTERATIONS
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 2B) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS
 AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION
 AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE
 REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY.
  
 2C) FBC* 110.3.9 RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD, MANAGER OF
 THE RESIDENT INSPECTOR PROGRAM. KEN CONRAD CONTACT
 INFORMATION:
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2D) SINCE THIS PROJECT WILL BE PART OF THE RESIDENT
 INSPECTOR PROGRAM A THIRD SET OF ALL PLANS AND
 SUPPORTING DOCUMENTS (ENERGY CALCULATIONS, SOILS
 REPORTS, PRODUCT APPROVALS ETC, WILL BE REQUIRED.
 107.3.1.
  
 NOTE, FORMS WERE E-MAILED TO :
 [email protected]
  
 3) MISSING SOILS REPORTS, 2010 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 4) SUBMIT (3) COPIES. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP
 INSULATION
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, A/C ROOF CURBS AND ADAPTORS
  
 5) THE COVER SHEET LIST PRODUCT APPROVALS REQUIRED BY
 THE DESIGNER OF RECORD, ALL LISTED ARE FLORIDA
 APPROVALS ONLY, NONE OF THE PRODUCTS HAVE BEEN REVIEWED
 BY THE DESIGNER OF RECORD . 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) THE ROOFING REPORT SUBMITTED FL 5680-R9, LISTED IN
 THE DESIGNER OF ECORDS LIST IS THE MOST CURRENT REPORT
 FL 5680-R10.
  
 7) MIAMI-DADE NOA 140626.02 CARLISLE SURE WELD NOT ON
 THE DESINER OF RECODS LIST.
  
 8) FL 11537-R4 DOOR NOT IDENTIFIED NOR PRESSURES, ONLY
 ONE COPY SUBMITTED. MISSING INSTALATION INSTRUCTIONS.
  
 9) SUBMITTED FL 11749-R2 DESIGNER OF RECORD REQUESTED
 FL 14636-R3.
  
 10) SUBMITTED FL 13533-R4 UPDATE TO THE CURRENT FL
 13533-R5.
  
 11) SUBMITTED DRYVIT SYSTEMS 11-1108.02 & 12-0703.03
 MIAMI-DADE NOA, NOT ON LIST, NEVER REVIEWED.
  
 12) SUBMITTED 1 COPY OF FL 15110.1 MIAMI-DADE NOA
 IDENTIFY IF INSTALATION IS A "S" OR "NB" DOOR.
  
 13) NO WINDOW REPORTS, WALL LOUVERS AND PRE-ENGINEERED
 A/C STANDS WERE SUBMITTED.
  
 14)(A) THERE ARE DISCREPANCIES IN THE LS-1 EGRESS DOOR
 IDENTIFICATION PLAN VERSES THE CHART AT THE BOTTOM OF
 THE PAGE. DISCREPANCY DOORS ON THE PLANS 22 & 18 ARE
 NOT ON THE CHART AND ON THE CHART DOORS 21 & 19 ARE NOT
 ON THE PLAN.
  
 14)(B) DOOR # 17,18 & 19 ARE NOT ON THE CHART NOR IS
 DOOR OPENING TO THE LEFT IN THE VESTIBULE BETWEEN DOORS
 3 & 90, ARROWS SHOWING AN EGRESS PATH AND A EXIT SIGN
 SHOWN, NO DOOR IS IDENTIFIED. THE DOORS CAN NOT BE
 IDENTIFIED ON SHEET A5 SINCE THE STAPLES THAT BIND THE
 PLANS TOGETHER ARE OVER THE IDENTIFYING DOOR NUMBERS.
  
 14C) SHEET A-5 THE DOOR SCHEDULE IS IN THE UPPER LEFT
 HAND CORNER SO FAR THE STAPLES WILL NOT LET YOU
 IDENTIFY THE DOOR. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 14D) DOOR # 3 APPEARS TO BE (2) 48 INCH SWING DOORS.
 BOTH DOORS ARE MISSING THE 18" CLEARANCE FOR
 MANEUVERING CLEARANCES 2010 FL ACC CODE TABLE
 404.2.4.1.
  
 14E) PLEASE PROVIDE A SURVEY OR SITE PLAN, THE ISSUE IS
 IS THERE A PROPERTY LINE BETWEEN PUBLIX AND THE OTHER
 STORES, OR SITE PROPERTY LINE. THE DESIGN TEAM IS
 TAKING AN EXECPTION TO UNLIMITED AREA UNDER 507.4.
 507.5 REQUIRES 3 HR WALLS FOR WALLS WITH ONLY 40'-0"
 CLEAR.
  
 15) SHEET LS-1 VESTIBULE POSSIBLY 2 ELECTRIC CARTS ARE
 IN THE EGRESS PATH.
 2010 FBC-B 1003.3.3 HORIZONTAL PROJECTIONS. STRUCTURAL
 ELEMENTS, FIXTURES OR FURNISHINGS SHALL NOT PROJECT
 HORIZONTALLY FROM EITHER SIDE MORE THAN 4 INCHES (102
 MM) OVER ANY WALKING SURFACE BETWEEN THE HEIGHTS OF 27
 INCHES (686 MM) AND 80 INCHES (2032 MM) ABOVE THE
 WALKING SURFACE.
 2010 FBC-B 1003.3.4 CLEAR WIDTH. PROTRUDING OBJECTS
 SHALL NOT REDUCE THE MINIMUM CLEAR WIDTH OF ACCESSIBLE
 ROUTES.
  
 16) LS1 BETWEEN GRID LINE 1 & 2 THERE APPEARS TO BE AN
 EXIT WAY FROM THE FRONT OF THE BUILDING BUT IT STOPS
 MIDWAY THROUGH THE BUILDING. THEN AT THE REAR CORNER OF
 THE BUILDING THERE IS DOOR 25, IS THIS EXIT IN THE SAME
 CORRIDOR OR IS THE REAR OF THE NEXT BUILDING IN FRONT
 OF THE DOOR? PLEASE PROVIDE WHERE THIS CORRIDOR ENDS?
 1027.2 EXIT DISCHARGE CAPACITY/ 1027.3 EXIT DISCHARGE
 LOCATION.
  
 17) SHEET A-1 ALL EXTERIOR 12" BLOCK WALLS SHOW THEY
 ARE FOAM FILED, PLEASE PROVIDE PRODUCT INFORMATION FOR
 FOAM INSULATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 18A) SHEET A-1 DESIGN PRESSURES ARE IN V-ULT, THEY DO
 NOT PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 18B) PLEASE ALSO PROVIDE THE VASD PRESSURES SINCE ALL
 THE PRODUCT APPROVALS ARE IN VASD. 1609.3.1.
  
 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES
 FOR THE ROOF ZONE.
  
 19) SHEET A-2. DOORS 30 & 42 CAN NOT VERIFY THEIR FIRE
 RATING SINCE SHEET A5 THE NUMBER COLUMN IDENTIFYING THE
 DOORS IS STAPLED CAN NOT BE VIEWED UNDER THIS REVIEW.
 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 20A) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 &
 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE
 FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR
 ICYENE INSULATION. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4.1.2 (1-4) PROVIDE DOCUMENTATION.
  
 20B) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 &
 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE
 FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR
 ICYENE INSULATION. THE USE OF "OR" THE DESIGNER OF
 RECORD MUST DECIDE WHICH SYSTEM WILL BE INSTALLED.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 21) SHEET A-9 GRAB BAR HEIGHTS ARE NOT PROVIDED,
 PROVIDE COMPLIANCE WITH 2010 FBC- ACCESSIBILITY CODE
 609.4. POSITION OF GRAB BARS.
  
 22) SHEET A-17 SECTION THROUGH PHARMACY SHOWS AN
 OPTIONAL DRIVE-THRU WINDOW. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 23) SHEET A-17 SECTIONS THROUGH PHARMACY SHOW GYPSUM
 BOARD SUSPENSION SYSTEM CEILING, THE PLANS DO NOT
 INDICATE HOW THE SYSTEM IS TO BE SUSPENDED, ONLY THAT
 THE 1 1/2" C CHANNEL IS TO OCCUR AT 48 INCHES O.C.?
 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 2508.1
 GENERAL.
 GYPSUM BOARD AND GYPSUM PLASTER CONSTRUCTION SHALL BE
 OF THE MATERIALS LISTED IN TABLES 2506.2 AND 2507.2.
 THESE MATERIALS SHALL BE ASSEMBLED AND INSTALLED IN
 COMPLIANCE WITH THE APPROPRIATE STANDARDS LISTED IN
 TABLES 2508.1 AND 2511.1.1, AND CHAPTER 35.
  
 24) ADA-2 ATM MACHINES PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR FASTENING THE ATM MACHINE AND
 ANCHORING IT TO EITHER THE FLOOR OR WALL SYSTEM.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 25A) ADA-2 ATM MACHINES PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-ACCESS. CODE 707.2 CLEAR FLOOR OR GROUND
 SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 25B) 07.5 SPEECH OUTPUT. MACHINES SHALL BE SPEECH
 ENABLED. OPERATING INSTRUCTIONS AND ORIENTATION,
 VISIBLE TRANSACTION PROMPTS, USER INPUT VERIFICATION,
 ERROR MESSAGES, AND ALL DISPLAYED INFORMATION FOR FULL
 USE SHALL BE ACCESSIBLE TO AND INDEPENDENTLY USABLE BY
 INDIVIDUALS WITH VISION IMPAIRMENTS. SPEECH SHALL BE
 DELIVERED THROUGH A MECHANISM THAT IS READILY AVAILABLE
 TO ALL USERS, INCLUDING BUT NOT LIMITED TO, AN INDUSTRY
 STANDARD CONNECTOR OR A TELEPHONE HANDSET. SPEECH SHALL
 BE RECORDED OR DIGITIZED HUMAN, OR SYNTHESIZED.
  
 25C) 707.6.1 INPUT CONTROLS. AT LEAST ONE TACTILELY
 DISCERNIBLE INPUT CONTROL SHALL BE PROVIDED FOR EACH
 FUNCTION. WHERE PROVIDED, KEY SURFACES NOT ON ACTIVE
 AREAS OF DISPLAY SCREENS, SHALL BE RAISED ABOVE
 SURROUNDING SURFACES. WHERE MEMBRANE KEYS ARE THE ONLY
 METHOD OF INPUT, EACH SHALL BE TACTILELY DISCERNABLE
 FROM SURROUNDING SURFACES AND ADJACENT KEYS.
  
 25D) 707.6.2 NUMERIC KEYS. NUMERIC KEYS SHALL BE
 ARRANGED IN A 12-KEY ASCENDING OR DESCENDING TELEPHONE
 KEYPAD LAYOUT. THE NUMBER FIVE KEY SHALL BE TACTILELY
 DISTINCT FROM THE OTHER KEYS.
  
 26A) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW
 SCUPPERS PLEASE PROVIDE SIZING CALCULATIONS FOR BOTH
 THE SCUPPERS AND OVERFLOW SHALL COMPLY WITH SECTION
 1503 AND THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER
 11.
  
 26B) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW
 SCUPPERS PLEASE PROVIDE COMPLIANCE 1503.7 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 26C) SHEET RD-1 DETAIL (13) & SHEET S-4 DETAIL (2) A
 PITCH PAN DETAIL, PLEASE NOTE FOR A/C ROOFTOP
 COMPRESSORS PITCH PANS CAN NOT BE USED, COMPLIANCE WITH
 1509.7 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES
 (203 MM) ABOVE THE ROOF SURFACE (FINISH SURFACE, ALLOW
 FOR ROOF TOP INSULATION, AND UNIT OVER HANG OF CURB),
 OR WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON
 RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
  
 26D) SHEET RD-1 DETAIL (7) DOCK CANOPY GUTTER DETAIL
 PLEASE PROVIDE THE SIZING OF THE GUTTER AND THE TYPE OF
 FASTENERS FOR THE WEIGHT OF GUTTER AND RAINWATER RUN
 OFF. 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION
 DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR
 WALL ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE
 COMPLIANCE WITH THIS CODE. THE CONSTRUCTION DOCUMENTS
 SHALL PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS
 REQUIRED, INCLUDING FLASHING, INTERSECTIONS WITH
 DISSIMILAR MATERIALS, CORNERS, END DETAILS, CONTROL
 JOINTS, INTERSECTIONS AT ROOF, EAVES OR PARAPETS, MEANS
 OF DRAINAGE, WATER-RESISTIVE MEMBRANE AND DETAILS
 AROUND OPENINGS.
  
  
 27) SHEET RD-2 DETAIL # 3 ROOR TOP INSULATION DETAIL,
 DETAIL <37.5 PLEASE ELIMINATE THE MEN ROOF IS ABOVE 30
 FEET WITH THE TOP PORTION OF THE ROOF AT 31'-4" AND THE
 TOP OF THE PARAPET AT 34'-0" THIS IS LESS THAN 3'-0"
 AND CREATES CORNER ZONES. THE PLANS WILL NEED TO SHOW
 INSULATION FASTENING FOR FULL SHEETS AND HALF SHEETS
 FOR ZONES 1, 2 & 3 WITH THE ASSOCIATED PRESSURES FOR
 BOTH FULL SHEETS AND HALF SHEETS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 28) SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING ON THE
 ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST AND OR
 THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE ONCE THE
 ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 *******************************************************
 *******************************************************
 *********************************************
  
 ARCHITECTURAL PLANS SUBMITTED SUPPLEMENTAL DOCUMENTS BY
 MCG ARCHITECTURE
  
 29) ATAS WIND LOCK SUFFIT PANELS WILL REQUIRE A PRODUCT
 APPROVAL: 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, SOFFITS, EFIS SYSTEMS,
  
 30) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 (DESIGNER OF RECORD) PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 31) SHEET A201 AND 300 SERIES SHEETS INDICATE THE USE
 OF 5/8 INCH EXTERIOR GRADE PLYWOOD AS BACKING
 (SHEATHING) PLEASE SEE THE BUILDING IS DECLARED A TYPE
 IIB BUILDING. 03.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN
 ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
  
 1.1 FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
 UPDATE PLANS TO FIRE RETARDANT TREATED PLYWOOD.
  
 31) SEE A-300 SERIES SHEETS AND SHOW COMPLIANCE WITH
 2010 FBC-B 1406.2.4 FIREBLOCKING. WHERE THE COMBUSTIBLE
 EXTERIOR WALL COVERING IS FURRED FROM THE WALL AND
 FORMS A SOLID SURFACE, THE DISTANCE BETWEEN THE BACK OF
 THE COVERING AND THE WALL SHALL NOT EXCEED 15/8 INCHES
 (41 MM). WHERE REQUIRED BY SECTION 717, THE SPACE
 THEREBY CREATED SHALL BE FIREBLOCKED. ALSO SEE 717.2.6
 AND EXCEPTIONS.
  
 32) THE A-300 SERIES SHEETS SHOW THE USE OF EFIS
 SYSTEM, PLEASE SHOW COMPLIANCE WITH:
 2010 FBC-B 408.1 GENERAL.
 THE PROVISIONS OF THIS SECTION SHALL GOVERN THE
 MATERIALS, CONSTRUCTION AND QUALITY OF EXTERIOR
 INSULATION AND FINISH SYSTEMS (EIFS) FOR USE AS
 EXTERIOR WALL COVERINGS IN ADDITION TO OTHER APPLICABLE
 REQUIREMENTS OF CHAPTERS 7, 14, 16, 17 AND 26.
 1408.2 PERFORMANCE CHARACTERISTICS.
 EIFS SHALL BE CONSTRUCTED SUCH THAT IT MEETS THE
 PERFORMANCE CHARACTERISTICS REQUIRED IN ASTM E 2568.
 1408.3 STRUCTURAL DESIGN.
 THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED
 BY CHAPTER 16.
 1408.4 WEATHER RESISTANCE.
 EIFS SHALL COMPLY WITH SECTION 1403 AND SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN
 ACCORDANCE WITH THIS SECTION AND THE MA
 1408.4.1 EIFS WITH DRAINAGE.
 EIFS WITH DRAINAGE SHALL HAVE AN AVERAGE MINIMUM
 DRAINAGE EFFICIENCY OF 90 PERCENT WHEN TESTED IN
 ACCORDANCE THE REQUIREMENTS OF ASTM E 2273 AND IS
 REQUIRED ON FRAMED WALLS OF TYPE V CONSTRUCTION, GROUP
 R1, R2, R3 AND R4 OCCUPANCIES.
 1408.4.1.1 WATER-RESISTIVE BARRIER.
 FOR EIFS WITH DRAINAGE, THE WATER-RESISTIVE BARRIER
 SHALL COMPLY WITH SECTION 1404.2 OR ASTM E 2570.
 1408.5 INSTALLATION.
 INSTALLATION OF THE EIFS AND EIFS WITH DRAINAGE SHALL
 BE IN ACCORDANCE WITH THE EIFS MANUFACTURER?S
 INSTRUCTIONS.
  
 33) SHEET S001HAS COMPONENTS & CLADDING THAT ARE
 DIFFERENT FROM THOUGHS FOUND ON SHEET A-1 WHICH
 PRESSURES ARE TTO BE USED FORTHIS PROJECT? DISCREPANCY.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved