| 2014-09-30 11:21:01 | BUILDING PLAN REVIEW |
| | PERMIT: 14090659 |
| | ADD: 500 BELVEDERE RD |
| | CONT: TBD |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 30/ 2014 |
| | ACTION: DENIED |
| | |
| | NOTE! PLANS INDICATE THEY ARE ONLY 50% COMPLETE. A |
| | THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 1) THE PLANS SUBMITED SHOW TWO DIFFERENT SETS OF PLANS |
| | ,ONE HAS THE HEADING OF SUPPLEMENTAL DRAWINGS, BUT THEY |
| | ARE FROM A DIFFERENT ACHITECT, AND FIRM. PLEASE PROVIDE |
| | COMPLIANCE WITH FL. ADMINISTRATIVE CODE, 61G1-23.015 |
| | RESPONSIBLE SUPERVISING CONTROL OVER ARCHITECTURAL |
| | PRACTICE OUTSIDE OF THE ARCHITECT'S OFFICE. |
| | |
| | |
| | |
| | 2A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. |
| | THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR FOR: |
| | BUILDING TYPE II CONSTRUCTION |
| | FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT |
| | FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | 2B) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION |
| | AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE |
| | REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY. |
| | |
| | 2C) FBC* 110.3.9 RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD, MANAGER OF |
| | THE RESIDENT INSPECTOR PROGRAM. KEN CONRAD CONTACT |
| | INFORMATION: |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2D) SINCE THIS PROJECT WILL BE PART OF THE RESIDENT |
| | INSPECTOR PROGRAM A THIRD SET OF ALL PLANS AND |
| | SUPPORTING DOCUMENTS (ENERGY CALCULATIONS, SOILS |
| | REPORTS, PRODUCT APPROVALS ETC, WILL BE REQUIRED. |
| | 107.3.1. |
| | |
| | NOTE, FORMS WERE E-MAILED TO : |
| | [email protected] |
| | |
| | 3) MISSING SOILS REPORTS, 2010 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| | OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 4) SUBMIT (3) COPIES. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP |
| | INSULATION |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS, A/C ROOF CURBS AND ADAPTORS |
| | |
| | 5) THE COVER SHEET LIST PRODUCT APPROVALS REQUIRED BY |
| | THE DESIGNER OF RECORD, ALL LISTED ARE FLORIDA |
| | APPROVALS ONLY, NONE OF THE PRODUCTS HAVE BEEN REVIEWED |
| | BY THE DESIGNER OF RECORD . 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) THE ROOFING REPORT SUBMITTED FL 5680-R9, LISTED IN |
| | THE DESIGNER OF ECORDS LIST IS THE MOST CURRENT REPORT |
| | FL 5680-R10. |
| | |
| | 7) MIAMI-DADE NOA 140626.02 CARLISLE SURE WELD NOT ON |
| | THE DESINER OF RECODS LIST. |
| | |
| | 8) FL 11537-R4 DOOR NOT IDENTIFIED NOR PRESSURES, ONLY |
| | ONE COPY SUBMITTED. MISSING INSTALATION INSTRUCTIONS. |
| | |
| | 9) SUBMITTED FL 11749-R2 DESIGNER OF RECORD REQUESTED |
| | FL 14636-R3. |
| | |
| | 10) SUBMITTED FL 13533-R4 UPDATE TO THE CURRENT FL |
| | 13533-R5. |
| | |
| | 11) SUBMITTED DRYVIT SYSTEMS 11-1108.02 & 12-0703.03 |
| | MIAMI-DADE NOA, NOT ON LIST, NEVER REVIEWED. |
| | |
| | 12) SUBMITTED 1 COPY OF FL 15110.1 MIAMI-DADE NOA |
| | IDENTIFY IF INSTALATION IS A "S" OR "NB" DOOR. |
| | |
| | 13) NO WINDOW REPORTS, WALL LOUVERS AND PRE-ENGINEERED |
| | A/C STANDS WERE SUBMITTED. |
| | |
| | 14)(A) THERE ARE DISCREPANCIES IN THE LS-1 EGRESS DOOR |
| | IDENTIFICATION PLAN VERSES THE CHART AT THE BOTTOM OF |
| | THE PAGE. DISCREPANCY DOORS ON THE PLANS 22 & 18 ARE |
| | NOT ON THE CHART AND ON THE CHART DOORS 21 & 19 ARE NOT |
| | ON THE PLAN. |
| | |
| | 14)(B) DOOR # 17,18 & 19 ARE NOT ON THE CHART NOR IS |
| | DOOR OPENING TO THE LEFT IN THE VESTIBULE BETWEEN DOORS |
| | 3 & 90, ARROWS SHOWING AN EGRESS PATH AND A EXIT SIGN |
| | SHOWN, NO DOOR IS IDENTIFIED. THE DOORS CAN NOT BE |
| | IDENTIFIED ON SHEET A5 SINCE THE STAPLES THAT BIND THE |
| | PLANS TOGETHER ARE OVER THE IDENTIFYING DOOR NUMBERS. |
| | |
| | 14C) SHEET A-5 THE DOOR SCHEDULE IS IN THE UPPER LEFT |
| | HAND CORNER SO FAR THE STAPLES WILL NOT LET YOU |
| | IDENTIFY THE DOOR. 2010 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 14D) DOOR # 3 APPEARS TO BE (2) 48 INCH SWING DOORS. |
| | BOTH DOORS ARE MISSING THE 18" CLEARANCE FOR |
| | MANEUVERING CLEARANCES 2010 FL ACC CODE TABLE |
| | 404.2.4.1. |
| | |
| | 14E) PLEASE PROVIDE A SURVEY OR SITE PLAN, THE ISSUE IS |
| | IS THERE A PROPERTY LINE BETWEEN PUBLIX AND THE OTHER |
| | STORES, OR SITE PROPERTY LINE. THE DESIGN TEAM IS |
| | TAKING AN EXECPTION TO UNLIMITED AREA UNDER 507.4. |
| | 507.5 REQUIRES 3 HR WALLS FOR WALLS WITH ONLY 40'-0" |
| | CLEAR. |
| | |
| | 15) SHEET LS-1 VESTIBULE POSSIBLY 2 ELECTRIC CARTS ARE |
| | IN THE EGRESS PATH. |
| | 2010 FBC-B 1003.3.3 HORIZONTAL PROJECTIONS. STRUCTURAL |
| | ELEMENTS, FIXTURES OR FURNISHINGS SHALL NOT PROJECT |
| | HORIZONTALLY FROM EITHER SIDE MORE THAN 4 INCHES (102 |
| | MM) OVER ANY WALKING SURFACE BETWEEN THE HEIGHTS OF 27 |
| | INCHES (686 MM) AND 80 INCHES (2032 MM) ABOVE THE |
| | WALKING SURFACE. |
| | 2010 FBC-B 1003.3.4 CLEAR WIDTH. PROTRUDING OBJECTS |
| | SHALL NOT REDUCE THE MINIMUM CLEAR WIDTH OF ACCESSIBLE |
| | ROUTES. |
| | |
| | 16) LS1 BETWEEN GRID LINE 1 & 2 THERE APPEARS TO BE AN |
| | EXIT WAY FROM THE FRONT OF THE BUILDING BUT IT STOPS |
| | MIDWAY THROUGH THE BUILDING. THEN AT THE REAR CORNER OF |
| | THE BUILDING THERE IS DOOR 25, IS THIS EXIT IN THE SAME |
| | CORRIDOR OR IS THE REAR OF THE NEXT BUILDING IN FRONT |
| | OF THE DOOR? PLEASE PROVIDE WHERE THIS CORRIDOR ENDS? |
| | 1027.2 EXIT DISCHARGE CAPACITY/ 1027.3 EXIT DISCHARGE |
| | LOCATION. |
| | |
| | 17) SHEET A-1 ALL EXTERIOR 12" BLOCK WALLS SHOW THEY |
| | ARE FOAM FILED, PLEASE PROVIDE PRODUCT INFORMATION FOR |
| | FOAM INSULATION. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 18A) SHEET A-1 DESIGN PRESSURES ARE IN V-ULT, THEY DO |
| | NOT PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B |
| | 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF |
| | ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 18B) PLEASE ALSO PROVIDE THE VASD PRESSURES SINCE ALL |
| | THE PRODUCT APPROVALS ARE IN VASD. 1609.3.1. |
| | |
| | 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES |
| | FOR THE ROOF ZONE. |
| | |
| | 19) SHEET A-2. DOORS 30 & 42 CAN NOT VERIFY THEIR FIRE |
| | RATING SINCE SHEET A5 THE NUMBER COLUMN IDENTIFYING THE |
| | DOORS IS STAPLED CAN NOT BE VIEWED UNDER THIS REVIEW. |
| | 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 20A) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 & |
| | 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE |
| | FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR |
| | ICYENE INSULATION. PLEASE PROVIDE COMPLIANCE WITH 2010 |
| | FBC-B 2603.4.1.2 (1-4) PROVIDE DOCUMENTATION. |
| | |
| | 20B) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 & |
| | 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE |
| | FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR |
| | ICYENE INSULATION. THE USE OF "OR" THE DESIGNER OF |
| | RECORD MUST DECIDE WHICH SYSTEM WILL BE INSTALLED. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 21) SHEET A-9 GRAB BAR HEIGHTS ARE NOT PROVIDED, |
| | PROVIDE COMPLIANCE WITH 2010 FBC- ACCESSIBILITY CODE |
| | 609.4. POSITION OF GRAB BARS. |
| | |
| | 22) SHEET A-17 SECTION THROUGH PHARMACY SHOWS AN |
| | OPTIONAL DRIVE-THRU WINDOW. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | 23) SHEET A-17 SECTIONS THROUGH PHARMACY SHOW GYPSUM |
| | BOARD SUSPENSION SYSTEM CEILING, THE PLANS DO NOT |
| | INDICATE HOW THE SYSTEM IS TO BE SUSPENDED, ONLY THAT |
| | THE 1 1/2" C CHANNEL IS TO OCCUR AT 48 INCHES O.C.? |
| | PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 2508.1 |
| | GENERAL. |
| | GYPSUM BOARD AND GYPSUM PLASTER CONSTRUCTION SHALL BE |
| | OF THE MATERIALS LISTED IN TABLES 2506.2 AND 2507.2. |
| | THESE MATERIALS SHALL BE ASSEMBLED AND INSTALLED IN |
| | COMPLIANCE WITH THE APPROPRIATE STANDARDS LISTED IN |
| | TABLES 2508.1 AND 2511.1.1, AND CHAPTER 35. |
| | |
| | 24) ADA-2 ATM MACHINES PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATIONS FOR FASTENING THE ATM MACHINE AND |
| | ANCHORING IT TO EITHER THE FLOOR OR WALL SYSTEM. |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 25A) ADA-2 ATM MACHINES PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-ACCESS. CODE 707.2 CLEAR FLOOR OR GROUND |
| | SPACE. |
| | A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL |
| | BE PROVIDED. |
| | |
| | 25B) 07.5 SPEECH OUTPUT. MACHINES SHALL BE SPEECH |
| | ENABLED. OPERATING INSTRUCTIONS AND ORIENTATION, |
| | VISIBLE TRANSACTION PROMPTS, USER INPUT VERIFICATION, |
| | ERROR MESSAGES, AND ALL DISPLAYED INFORMATION FOR FULL |
| | USE SHALL BE ACCESSIBLE TO AND INDEPENDENTLY USABLE BY |
| | INDIVIDUALS WITH VISION IMPAIRMENTS. SPEECH SHALL BE |
| | DELIVERED THROUGH A MECHANISM THAT IS READILY AVAILABLE |
| | TO ALL USERS, INCLUDING BUT NOT LIMITED TO, AN INDUSTRY |
| | STANDARD CONNECTOR OR A TELEPHONE HANDSET. SPEECH SHALL |
| | BE RECORDED OR DIGITIZED HUMAN, OR SYNTHESIZED. |
| | |
| | 25C) 707.6.1 INPUT CONTROLS. AT LEAST ONE TACTILELY |
| | DISCERNIBLE INPUT CONTROL SHALL BE PROVIDED FOR EACH |
| | FUNCTION. WHERE PROVIDED, KEY SURFACES NOT ON ACTIVE |
| | AREAS OF DISPLAY SCREENS, SHALL BE RAISED ABOVE |
| | SURROUNDING SURFACES. WHERE MEMBRANE KEYS ARE THE ONLY |
| | METHOD OF INPUT, EACH SHALL BE TACTILELY DISCERNABLE |
| | FROM SURROUNDING SURFACES AND ADJACENT KEYS. |
| | |
| | 25D) 707.6.2 NUMERIC KEYS. NUMERIC KEYS SHALL BE |
| | ARRANGED IN A 12-KEY ASCENDING OR DESCENDING TELEPHONE |
| | KEYPAD LAYOUT. THE NUMBER FIVE KEY SHALL BE TACTILELY |
| | DISTINCT FROM THE OTHER KEYS. |
| | |
| | 26A) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW |
| | SCUPPERS PLEASE PROVIDE SIZING CALCULATIONS FOR BOTH |
| | THE SCUPPERS AND OVERFLOW SHALL COMPLY WITH SECTION |
| | 1503 AND THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER |
| | 11. |
| | |
| | 26B) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW |
| | SCUPPERS PLEASE PROVIDE COMPLIANCE 1503.7 PROTECTION |
| | AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 26C) SHEET RD-1 DETAIL (13) & SHEET S-4 DETAIL (2) A |
| | PITCH PAN DETAIL, PLEASE NOTE FOR A/C ROOFTOP |
| | COMPRESSORS PITCH PANS CAN NOT BE USED, COMPLIANCE WITH |
| | 1509.7 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL UNITS |
| | SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES |
| | (203 MM) ABOVE THE ROOF SURFACE (FINISH SURFACE, ALLOW |
| | FOR ROOF TOP INSULATION, AND UNIT OVER HANG OF CURB), |
| | OR WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON |
| | RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| | |
| | |
| | 26D) SHEET RD-1 DETAIL (7) DOCK CANOPY GUTTER DETAIL |
| | PLEASE PROVIDE THE SIZING OF THE GUTTER AND THE TYPE OF |
| | FASTENERS FOR THE WEIGHT OF GUTTER AND RAINWATER RUN |
| | OFF. 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION |
| | DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR |
| | WALL ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE |
| | COMPLIANCE WITH THIS CODE. THE CONSTRUCTION DOCUMENTS |
| | SHALL PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS |
| | REQUIRED, INCLUDING FLASHING, INTERSECTIONS WITH |
| | DISSIMILAR MATERIALS, CORNERS, END DETAILS, CONTROL |
| | JOINTS, INTERSECTIONS AT ROOF, EAVES OR PARAPETS, MEANS |
| | OF DRAINAGE, WATER-RESISTIVE MEMBRANE AND DETAILS |
| | AROUND OPENINGS. |
| | |
| | |
| | 27) SHEET RD-2 DETAIL # 3 ROOR TOP INSULATION DETAIL, |
| | DETAIL <37.5 PLEASE ELIMINATE THE MEN ROOF IS ABOVE 30 |
| | FEET WITH THE TOP PORTION OF THE ROOF AT 31'-4" AND THE |
| | TOP OF THE PARAPET AT 34'-0" THIS IS LESS THAN 3'-0" |
| | AND CREATES CORNER ZONES. THE PLANS WILL NEED TO SHOW |
| | INSULATION FASTENING FOR FULL SHEETS AND HALF SHEETS |
| | FOR ZONES 1, 2 & 3 WITH THE ASSOCIATED PRESSURES FOR |
| | BOTH FULL SHEETS AND HALF SHEETS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.2 FOR |
| | ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 28) SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING ON THE |
| | ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST AND OR |
| | THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE ONCE THE |
| | ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2 FOR ROOF |
| | ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | ******************************************************* |
| | ******************************************************* |
| | ********************************************* |
| | |
| | ARCHITECTURAL PLANS SUBMITTED SUPPLEMENTAL DOCUMENTS BY |
| | MCG ARCHITECTURE |
| | |
| | 29) ATAS WIND LOCK SUFFIT PANELS WILL REQUIRE A PRODUCT |
| | APPROVAL: 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, SOFFITS, EFIS SYSTEMS, |
| | |
| | 30) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | (DESIGNER OF RECORD) PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 31) SHEET A201 AND 300 SERIES SHEETS INDICATE THE USE |
| | OF 5/8 INCH EXTERIOR GRADE PLYWOOD AS BACKING |
| | (SHEATHING) PLEASE SEE THE BUILDING IS DECLARED A TYPE |
| | IIB BUILDING. 03.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| | MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| | II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| | ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| | |
| | 1.1 FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES, |
| | FRAMING AND DECKING. |
| | UPDATE PLANS TO FIRE RETARDANT TREATED PLYWOOD. |
| | |
| | 31) SEE A-300 SERIES SHEETS AND SHOW COMPLIANCE WITH |
| | 2010 FBC-B 1406.2.4 FIREBLOCKING. WHERE THE COMBUSTIBLE |
| | EXTERIOR WALL COVERING IS FURRED FROM THE WALL AND |
| | FORMS A SOLID SURFACE, THE DISTANCE BETWEEN THE BACK OF |
| | THE COVERING AND THE WALL SHALL NOT EXCEED 15/8 INCHES |
| | (41 MM). WHERE REQUIRED BY SECTION 717, THE SPACE |
| | THEREBY CREATED SHALL BE FIREBLOCKED. ALSO SEE 717.2.6 |
| | AND EXCEPTIONS. |
| | |
| | 32) THE A-300 SERIES SHEETS SHOW THE USE OF EFIS |
| | SYSTEM, PLEASE SHOW COMPLIANCE WITH: |
| | 2010 FBC-B 408.1 GENERAL. |
| | THE PROVISIONS OF THIS SECTION SHALL GOVERN THE |
| | MATERIALS, CONSTRUCTION AND QUALITY OF EXTERIOR |
| | INSULATION AND FINISH SYSTEMS (EIFS) FOR USE AS |
| | EXTERIOR WALL COVERINGS IN ADDITION TO OTHER APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 7, 14, 16, 17 AND 26. |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | EIFS SHALL BE CONSTRUCTED SUCH THAT IT MEETS THE |
| | PERFORMANCE CHARACTERISTICS REQUIRED IN ASTM E 2568. |
| | 1408.3 STRUCTURAL DESIGN. |
| | THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL |
| | BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED |
| | BY CHAPTER 16. |
| | 1408.4 WEATHER RESISTANCE. |
| | EIFS SHALL COMPLY WITH SECTION 1403 AND SHALL BE |
| | DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN |
| | ACCORDANCE WITH THIS SECTION AND THE MA |
| | 1408.4.1 EIFS WITH DRAINAGE. |
| | EIFS WITH DRAINAGE SHALL HAVE AN AVERAGE MINIMUM |
| | DRAINAGE EFFICIENCY OF 90 PERCENT WHEN TESTED IN |
| | ACCORDANCE THE REQUIREMENTS OF ASTM E 2273 AND IS |
| | REQUIRED ON FRAMED WALLS OF TYPE V CONSTRUCTION, GROUP |
| | R1, R2, R3 AND R4 OCCUPANCIES. |
| | 1408.4.1.1 WATER-RESISTIVE BARRIER. |
| | FOR EIFS WITH DRAINAGE, THE WATER-RESISTIVE BARRIER |
| | SHALL COMPLY WITH SECTION 1404.2 OR ASTM E 2570. |
| | 1408.5 INSTALLATION. |
| | INSTALLATION OF THE EIFS AND EIFS WITH DRAINAGE SHALL |
| | BE IN ACCORDANCE WITH THE EIFS MANUFACTURER?S |
| | INSTRUCTIONS. |
| | |
| | 33) SHEET S001HAS COMPONENTS & CLADDING THAT ARE |
| | DIFFERENT FROM THOUGHS FOUND ON SHEET A-1 WHICH |
| | PRESSURES ARE TTO BE USED FORTHIS PROJECT? DISCREPANCY. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |